| 2004-04-06 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04031063 | | | ADD: 1609 S DIXIE# 3 | | | CONT: SARRI CONSTRUCTION | | | TEL: (561)315-9376 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 11-4.35.2 THE MINIMUM CLEAR OPENING FOR | | | A DRESSING ROOM WITH A CURTAIN IS 32". | | | | | | 11-4.35.4 EVERY ACCESSIBLE DRESSING ROOM | | | SHALL HAVE A 24"X48" BENCH FIXED TO THE | | | WALL ALONG THE LONGER DIMENSION. | | | BENCH SHALL BE MOUNTED BETWEEN 17" & | | | 19". | | | | | | PROVIDE ADDITIONAL INFORMATION AS TO | | | HOW THE SOFFIT FRAMING IS ATTACHED TO | | | WHAT STRUCTURE ABOVE? AT WHAT SPACING? | | | WHAT TYPE OF FAASTENERS? | | | | | | HOW WILL ACCESS TO AIR HANDLIER BE | | | ACHIEVED? | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|