| 2004-04-22 00:00:00 | DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE TOTAL SQUARE FEET OF A/C AREA ON |
| | THE PLANS IS INCORRECT ON SHEET 3. IT |
| | SHOULD BE 3410 SQFT. |
| | |
| | 3) SPECIFY THE ATTIC LIVE LOAD ON THE |
| | PLANS. SEE FBC TABLE 1604.1. |
| | |
| | 4) FOR CLARITY, PLEASE INDICATE WHICH |
| | CONNECTORS ARE FOR THE FLOOR TRUSSES ON |
| | THE TRUSS TIE DOWN LAYOUT ON SHEET 9. |
| | |
| | 5) SUBMIT STATE PRODUCT APPROVAL FOR THE |
| | COLLIER GARAGE DOOR WITH APPROVED STATUS |
| | |
| | 6) SUBMIT STATE OR LOCAL PRODUCT |
| | APPROVAL FOR THE 8'X7' GARAGE DOOR. |
| | |
| | 7) THE TRUSS ANCHOR SCHEDULE ON SHEET 9 |
| | LISTS A NUE-VUE 48 CONNECTOR. THE STATE |
| | PRODUCT APPROVAL SUBMITTED IS FOR A |
| | NVRT 48 OR NVSTA 22. PLEASE CLARIFY. |
| | |
| | 8) THE TRUSS CONNECTOR SCHEDULE LIST A |
| | SIMPSON HUC 412 WITH 1505# OF UPLIFT. |
| | THE CATALOG LISTS 905# FOR A HU412. |
| | SHOULD THIS BE A HUC 410,WHICH HAS A |
| | 1505# UPLIFT. |
| | |
| | 9) THE SUBMITTAL FOR THE BUTT GLASS |
| | WINDOW IS INCOMPLETE & CONTAINS ERRORS. |
| | THE QUAILITY ASSURANCE IS REQUIRED. THE |
| | LOT NUMBER IS INCORRECT. SPECIFY THE |
| | DESIGN PRESSURES AND LIMITATIONS. SUBMIT |
| | THE CALCULATIONS. SUBMIT THE SPECS. FOR |
| | THE GE SILICONE. |
| | |