Plan Review Notes
Plan Review Notes For Permit 04030977
Permit Number 04030977
Review Stop B
Sequence Number 1
Notes
Date Text
2004-04-22 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE TOTAL SQUARE FEET OF A/C AREA ON
 THE PLANS IS INCORRECT ON SHEET 3. IT
 SHOULD BE 3410 SQFT.
  
 3) SPECIFY THE ATTIC LIVE LOAD ON THE
 PLANS. SEE FBC TABLE 1604.1.
  
 4) FOR CLARITY, PLEASE INDICATE WHICH
 CONNECTORS ARE FOR THE FLOOR TRUSSES ON
 THE TRUSS TIE DOWN LAYOUT ON SHEET 9.
  
 5) SUBMIT STATE PRODUCT APPROVAL FOR THE
 COLLIER GARAGE DOOR WITH APPROVED STATUS
  
 6) SUBMIT STATE OR LOCAL PRODUCT
 APPROVAL FOR THE 8'X7' GARAGE DOOR.
  
 7) THE TRUSS ANCHOR SCHEDULE ON SHEET 9
 LISTS A NUE-VUE 48 CONNECTOR. THE STATE
 PRODUCT APPROVAL SUBMITTED IS FOR A
 NVRT 48 OR NVSTA 22. PLEASE CLARIFY.
  
 8) THE TRUSS CONNECTOR SCHEDULE LIST A
 SIMPSON HUC 412 WITH 1505# OF UPLIFT.
 THE CATALOG LISTS 905# FOR A HU412.
 SHOULD THIS BE A HUC 410,WHICH HAS A
 1505# UPLIFT.
  
 9) THE SUBMITTAL FOR THE BUTT GLASS
 WINDOW IS INCOMPLETE & CONTAINS ERRORS.
 THE QUAILITY ASSURANCE IS REQUIRED. THE
 LOT NUMBER IS INCORRECT. SPECIFY THE
 DESIGN PRESSURES AND LIMITATIONS. SUBMIT
 THE CALCULATIONS. SUBMIT THE SPECS. FOR
 THE GE SILICONE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714