2004-05-05 00:00:00********* UNSAT **********
  
 1)NOTE: PLEASE SEE THIS SET OF PLANS
 MENTIONS WORK TO BE DONE UNDER OTHER
 PERMIT? YET, THE OTHER PLANS THAT WERE
 SUBMITTED FOR REVIEW UNDER PERMI #
 04040499 ARE NOT SIGNED OFF FOR ELECTRIC
 -AL REVIEW.
 PLEASE SEE CODE COMPLIANCE ISSUES UNDER
 OTHER PERMIT #.
  
 2)NOTE: PLEASE SEE 225.31 FOR MEANS
 OF DISC REQ'D AT DEATCHED BLDG.
 SHOWS PANEL AS 60A FEED BUT DOES NOT
 INDICATE MCB ?
  
 3)NOTE: PLEASE SEE CWP HAS BEEN ADDED
 TO GROUNDING SSYTEM AT BLDG, YET NEW
 FOOTER STEEL IS ALSO REQ'D TO BE BONDED.
 250.32
  
 ONLY A NOTE: PLEASE VERIFY 2/0`S SHOWN
 FOR 150A PANEL. IF SHOWN THEN 2/0'S
 WILL BE REQ'D TO BE INSTALLED.
  
 PLEASE CORRELATE BOTH PERMITS AND PLANS
 AND CORRELATE #'S REFERENCED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  