| Plan Review Notes For Permit 04030953 |
| Permit Number |
04030953 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-05-05 00:00:00 | ********* UNSAT ********** | | | | | | 1)NOTE: PLEASE SEE THIS SET OF PLANS | | | MENTIONS WORK TO BE DONE UNDER OTHER | | | PERMIT? YET, THE OTHER PLANS THAT WERE | | | SUBMITTED FOR REVIEW UNDER PERMI # | | | 04040499 ARE NOT SIGNED OFF FOR ELECTRIC | | | -AL REVIEW. | | | PLEASE SEE CODE COMPLIANCE ISSUES UNDER | | | OTHER PERMIT #. | | | | | | 2)NOTE: PLEASE SEE 225.31 FOR MEANS | | | OF DISC REQ'D AT DEATCHED BLDG. | | | SHOWS PANEL AS 60A FEED BUT DOES NOT | | | INDICATE MCB ? | | | | | | 3)NOTE: PLEASE SEE CWP HAS BEEN ADDED | | | TO GROUNDING SSYTEM AT BLDG, YET NEW | | | FOOTER STEEL IS ALSO REQ'D TO BE BONDED. | | | 250.32 | | | | | | ONLY A NOTE: PLEASE VERIFY 2/0`S SHOWN | | | FOR 150A PANEL. IF SHOWN THEN 2/0'S | | | WILL BE REQ'D TO BE INSTALLED. | | | | | | PLEASE CORRELATE BOTH PERMITS AND PLANS | | | AND CORRELATE #'S REFERENCED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|