Date Text
2004-08-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04030950
 ADD: 753 N COGRESS AV
 CONT: WCI COMMUNITIES INC
 TEL: (561)775-2120
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PROVIDE DETAILS OF HOW TRANSITION WIL
 L BE MADE FROM RETAINING WALL TO THE
 DOOR OPENING OF THE SALES TRAILER. ACCES
 SIBLE OPENING MUST MEET REQUIREMENTS OF
 CHANGE INLEVEL 11-4.3.8. THIS COMMENT
 IS #6 FROM FIRST REVIEW.
  
 2) COMMENT#8 FROM 1ST REVIEW, S-4 FASTEN
 ER SCHEDULE IS FOR THE HIGH VELOCITY
 HURRICANE ZONE CORRECT. NOTE WIRE LATH
 IS APPLIED AS TO 2504.2.2. WHICH REFERS
 TO ASTM C-1063 HORIZONTAL 3/8" RIB LATH
 REQUIRES NAILS TO BE ENBEDED 1 3/4" INTO
 HORIZONTAL FRAMING MEMBERS @ EACH RIB
 (4") O.C. ASA AN EXAMPLE.
  
 3) COMMENT# 10 FROM 1ST REVIEW:
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ANCHORS
 B) ROOFING ASSEMBLIES
 C) BAHAMA SHUTTERS
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026