2004-04-16 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04030950
 ADD: 753 N CONGRESS AV
 CONT: WCI COMMUNITIES INC
 TEL: (561)775-2120
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITEY KNOWN, OR IS IN
 QUESTIONTHE BUILDING OFFICIAL MAY
 REQUIRE EXPLORATIONS, TEST OR OTHER
 ADEQUATE PROOF AS TO THE PERMISSIBLE
 SAFE BEARING CAPACITY.
 REQUIRED TEST AND RECOMMENDATIONS
 SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) SALES TRAILER;ACCESSIBLE ROUTE
 11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENETRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY. INDICATE THE ACCESSIBLE ROUTE
 FROM PUBLIC TRANSPORTATION.
  
 4)ACCESSIBLE ROUTE SIDEWALKS:SLOPE
 THE SHEET S-2 INDICATES THE SLOPE OF
 THESIDEWALKS. 11-4.3.7 CROSS SLOPE IS
 NOT
 TO EXCEED 1:50. PLANS INDICATE FOR A
 60" WIDE SIDEWALK TO BE 2 1/4".
  
 5) S-1 INDICATES THE USE OF A RETAINING
 WALL ON THREE SIDES OF THE BUILDING.
 SHOW COMPLIANCE WITH 1804.6.3.1
 OPENINGSSHALL BE ARRANGED TO PROVIDE
 CROSS VENTILATION. PROVIDE INFORMATION
 ON HOW CROSS VENTILATION SHALL OCCUR.
  
 6) PROVIDE DETAIL OF HOW TRANSITION WILL
 BE MADE FROM RETAINING WALL TO DOOR OPEN
 ING OF SALES CENTER. ACCESSIBLE OPENING
 MUST MEET REQUIREMENTS OF CHANG IN LEVEL
 11-4.3.8.
 SHEET A-5 DETAIL5 INDICATES A THRESHOLD
 BUT THERE IS NO CORRELATION TO LOCATION
 OF TRAILER SIDEWALL OR RETAINING WALL.
  
 7) THE TOWER STRUCTURES NEED TO INDICATE
 THE WIND DESIGN CRITERIA OF WHICH THEY
 ARE DESIGNED:
 FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 THE INTERNAL PRESSURE COEFFICIENT WILL
 BE FORE A OPEN BUILDING NOT ANENCLOSED
  
 8) S-4 FASTENER SCHEDULES ARE FOR THE
 HIGH VELOCITY HURRICANE ZONES, WE ARE
 NOT LOCATED IN THIS ZONE.
  
 9) 104.2.1 W.P.B. ADMINISTRATIVE CODE
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC
 AND THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE
 TERM "LEGAL" OR ITS RQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION".
  
 10) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 11)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ANCHORS,CONCRETE/ WOOD,
 WOOD/ WOOD
 B) BAHAMA SHUTTER
 C) ROOFING ASSEMBLY
  
 BUILDING PLAN REVIEW