| 2004-04-16 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04030950 |
| | ADD: 753 N CONGRESS AV |
| | CONT: WCI COMMUNITIES INC |
| | TEL: (561)775-2120 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | WHERE THE BEARING CAPACITY OF THE SOIL |
| | IS NOT DEFINITEY KNOWN, OR IS IN |
| | QUESTIONTHE BUILDING OFFICIAL MAY |
| | REQUIRE EXPLORATIONS, TEST OR OTHER |
| | ADEQUATE PROOF AS TO THE PERMISSIBLE |
| | SAFE BEARING CAPACITY. |
| | REQUIRED TEST AND RECOMMENDATIONS |
| | SUBMITTED TO VERIFY BEARING CAPA- |
| | CITY SHALL BE CERTIFIED BY A GEOTECH- |
| | NICALREPORT FROM A DESIGN PROFESSIONAL |
| | PROPERLY LICENSED IN THE STATE OF |
| | FLORIDA. |
| | |
| | 3) SALES TRAILER;ACCESSIBLE ROUTE |
| | 11-4.1.3(1) AT LEAST ONE ACCESSIBLE |
| | ROUTTE COMPLYING WITH 11-4.3 SHALL |
| | CONNECT ACCESSIBLE BUILDING OR FACILITY |
| | ENETRANCES WITH ALL ACCESSIBLE SPACES |
| | AND ELEMENTS WITHIN THE BUILDING OR |
| | FACILITY. INDICATE THE ACCESSIBLE ROUTE |
| | FROM PUBLIC TRANSPORTATION. |
| | |
| | 4)ACCESSIBLE ROUTE SIDEWALKS:SLOPE |
| | THE SHEET S-2 INDICATES THE SLOPE OF |
| | THESIDEWALKS. 11-4.3.7 CROSS SLOPE IS |
| | NOT |
| | TO EXCEED 1:50. PLANS INDICATE FOR A |
| | 60" WIDE SIDEWALK TO BE 2 1/4". |
| | |
| | 5) S-1 INDICATES THE USE OF A RETAINING |
| | WALL ON THREE SIDES OF THE BUILDING. |
| | SHOW COMPLIANCE WITH 1804.6.3.1 |
| | OPENINGSSHALL BE ARRANGED TO PROVIDE |
| | CROSS VENTILATION. PROVIDE INFORMATION |
| | ON HOW CROSS VENTILATION SHALL OCCUR. |
| | |
| | 6) PROVIDE DETAIL OF HOW TRANSITION WILL |
| | BE MADE FROM RETAINING WALL TO DOOR OPEN |
| | ING OF SALES CENTER. ACCESSIBLE OPENING |
| | MUST MEET REQUIREMENTS OF CHANG IN LEVEL |
| | 11-4.3.8. |
| | SHEET A-5 DETAIL5 INDICATES A THRESHOLD |
| | BUT THERE IS NO CORRELATION TO LOCATION |
| | OF TRAILER SIDEWALL OR RETAINING WALL. |
| | |
| | 7) THE TOWER STRUCTURES NEED TO INDICATE |
| | THE WIND DESIGN CRITERIA OF WHICH THEY |
| | ARE DESIGNED: |
| | FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | THE INTERNAL PRESSURE COEFFICIENT WILL |
| | BE FORE A OPEN BUILDING NOT ANENCLOSED |
| | |
| | 8) S-4 FASTENER SCHEDULES ARE FOR THE |
| | HIGH VELOCITY HURRICANE ZONES, WE ARE |
| | NOT LOCATED IN THIS ZONE. |
| | |
| | 9) 104.2.1 W.P.B. ADMINISTRATIVE CODE |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR |
| | OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES. |
| | SUCH INFORMATION SHALL BE SPECIFIC |
| | AND THE TECHNICAL CODES "SHALL NOT BE |
| | CITED AS A WHOLE OR IN PART, NOR THE |
| | TERM "LEGAL" OR ITS RQUIVALENT BE USED |
| | AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". |
| | |
| | 10) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 11)FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) TRUSS ANCHORS,CONCRETE/ WOOD, |
| | WOOD/ WOOD |
| | B) BAHAMA SHUTTER |
| | C) ROOFING ASSEMBLY |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |