Plan Review Notes
Plan Review Notes For Permit 04030910
Permit Number 04030910
Review Stop P
Sequence Number 2
Notes
Date Text
2005-04-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 2) ALL ARCHITECTURAL SHEETS, THE TITLE
 BLOCK MUST, AT A MINIMUM, CONTAIN THE
 FOLLOWING INFORMATION:
 PRINTED NAME OF THE PERSON SEALING THE
 DOCUMENT. 61G1-16.004(6)
 5) THS A1 DETAIL #2 SINK SHALL BE
 ACCESSIBLE. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. RESPONSE NOTED BUT THE
 FOLLOWING INFORMATION IS STILL REQUIRED:
 A. KNEE CLEARANCE 11-4.24.3
 B. SINK DEPTH 11-4.24.4
 C. CLEAR FLOOR SPACE 11-4.24.5 FORWARD
 APPROACH REQUIRED.
 D. EXPOSED PIPES & SURFACES 11-4.24.6
 E. FAUCETS 11-4.24.7
 6) SHT A1 DETAIL #3 TOILET ROOM SHALL BE
 ACCESSIBLE. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH SECTIONS 11-4.16,
 11-4.19, & 11-4.22 AND ALL SUBSECTIONS.
 RESPONSE NOTED, BUT SECTION 11-4.1.3(5)
 ITEM 3 REFERS TO VERTICAL ACCESSIBILITY
 AND THESE ARE EXCEPTIONS FOR VERTICAL
 ACCESSIBLITY ONLY.
 7) SHT A2 WHITE OUT AND HAND DRAWN
 CHANGES TO SIGNED/SEALED PLANS ARE NOT
 APPROVED. NEW SHEETS WITH CHANGES ARE
 REQUIRED. SECTION 104.2.1.3.
 ****************NEW COMMENT*************
 1B) INDEX OF DRAWINGS INDICATES SHEET
 FP-1 FIRE PROTECTION PLANS, BUT THIS
 SHEET IS NOT IN THE SETS OF PLANS.
 PLEASE CLARIFY. SECTION 104.2.1.