| 2005-04-23 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 BUILDING |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | FROM PREVIOUS REVIEW: |
| | 2) ALL ARCHITECTURAL SHEETS, THE TITLE |
| | BLOCK MUST, AT A MINIMUM, CONTAIN THE |
| | FOLLOWING INFORMATION: |
| | PRINTED NAME OF THE PERSON SEALING THE |
| | DOCUMENT. 61G1-16.004(6) |
| | 5) THS A1 DETAIL #2 SINK SHALL BE |
| | ACCESSIBLE. SUBMIT A DETAIL SHOWING |
| | COMPLIANCE WITH SECTION 11-4.24 AND ALL |
| | SUBSECTIONS. RESPONSE NOTED BUT THE |
| | FOLLOWING INFORMATION IS STILL REQUIRED: |
| | A. KNEE CLEARANCE 11-4.24.3 |
| | B. SINK DEPTH 11-4.24.4 |
| | C. CLEAR FLOOR SPACE 11-4.24.5 FORWARD |
| | APPROACH REQUIRED. |
| | D. EXPOSED PIPES & SURFACES 11-4.24.6 |
| | E. FAUCETS 11-4.24.7 |
| | 6) SHT A1 DETAIL #3 TOILET ROOM SHALL BE |
| | ACCESSIBLE. SUBMIT A DETAIL SHOWING |
| | COMPLIANCE WITH SECTIONS 11-4.16, |
| | 11-4.19, & 11-4.22 AND ALL SUBSECTIONS. |
| | RESPONSE NOTED, BUT SECTION 11-4.1.3(5) |
| | ITEM 3 REFERS TO VERTICAL ACCESSIBILITY |
| | AND THESE ARE EXCEPTIONS FOR VERTICAL |
| | ACCESSIBLITY ONLY. |
| | 7) SHT A2 WHITE OUT AND HAND DRAWN |
| | CHANGES TO SIGNED/SEALED PLANS ARE NOT |
| | APPROVED. NEW SHEETS WITH CHANGES ARE |
| | REQUIRED. SECTION 104.2.1.3. |
| | ****************NEW COMMENT************* |
| | 1B) INDEX OF DRAWINGS INDICATES SHEET |
| | FP-1 FIRE PROTECTION PLANS, BUT THIS |
| | SHEET IS NOT IN THE SETS OF PLANS. |
| | PLEASE CLARIFY. SECTION 104.2.1. |