| 2005-04-06 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)SEE PREVIOUS LIST, ITEM #1. |
| | PROVIDE THE PRINTED NAME OF THE PERSON |
| | SEALING THE DOCUMENT, FS481, FAC61G1-16. |
| | |
| | 2.)THE OWNER ON THE APPLICATION |
| | DOESN'T MATCH OUR RECORDS.PLEASE |
| | PROVIDE A COPY OF THE DEED.THE NOC IS |
| | LACKING COMPLETE INFORMATION (LEGAL, |
| | OWNER ADDRESS) AND NEEDS TO BE RECORDED. |
| | |
| | 3.)SEE PREVIOUS LIST, ITEM #4. |
| | PROVIDE A DETAIL FOR THE SPIRAL STAIR. |
| | FBC104.2.1, "SUCH INFORMATION SHALL BE |
| | SPECIFIC, AND THE TECHNICAL CODES SHALL |
| | NOT BE CITED AS A WHOLE OR IN PART . . . |
| | AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION."THE DETAIL SHOULD INCLUDE |
| | DIRECTION, ALL DIMENSIONS, HANDRAIL |
| | INFORMATION TO SHOW COMPLIANCE WITH FBC |
| | 1007.8.2.1. |
| | |
| | 4.)SOME COMMENTS WERE ADDRESSED IN THE |
| | FORM OF A LETTER.THE PLANS SHOULD SHOW |
| | CODE COMPLIANCE.PLEASE INCORPORATE |
| | THESE COMMENTS AS A PART OF THE PLAN. |
| | |
| | 5.)DECLARE THE BUILDING TYPE ON THE |
| | PLAN.THE TRANSMITTAL LETTER STATED |
| | THAT IT IS TYPE IV UNPROTECTED.TYPE IV |
| | CONSTRUCTION DOES NOT ALLOW COMBUSTIBLES |
| | FOR FLOOR OR BEARING WALLS, FBC606 AND |
| | FBC TABLE 600.THE 1 HOUR REQUIREMENT |
| | YOU REFER TO IS IN YOUR MEMO IS FOR TYPE |
| | IV 1 HR PROTECTED.COMBUSTIBLES ARE |
| | STILL NOT ALLOWED IN TYPE IV 1 HR |
| | PROTECTED. |
| | |
| | 6.)THE TRANSMITTAL LETTER INDICATED |
| | THAT THE OCCUPANT LOAD WILL BE LESS THAN |
| | 5 AND NOT OPEN TO THE PUBLIC, EXEMPTING |
| | THIS JOB FROM VERTICAL ACCESSIBILITY. |
| | PLEASE INDICATE THIS ON THE PLAN. |
| | |
| | 7.)PLEASE SEE PRIOR REQUEST FOR |
| | EXITING INFORMATION.IT IS NOT CLEAR |
| | WHERE THE DOORS LABELLED "1" (A DOUBLE |
| | DOOR AT THE BASE OF THE STAIRS, A SINGLE |
| | DOOR NEXT TO THE SPIRAL STAIR) LEAD.DO |
| | THEY LEAD TO THE OUTSIDE OR TO OTHER |
| | INTERIOR SPACE?PLEASE EITHER PROVIDE A |
| | SITE PLAN OR MAKE A NOTE ON THE PLAN. |
| | |
| | 8.)SEE PREVIOUS LIST, SECOND FLOOR |
| | BATHROOM TO BE ADAPTABLE, |
| | FBC11-4.1.3(11).THE EXCEPTION FOR |
| | VERTICAL ACCESSIBILITY DOES NOT WAIVE |
| | THE REQUIREMENT FOR ADAPTABILITY |
| | (ABILITY FOR FUTURE GRAB BARS IF |
| | NECESSARY) IN THE BATHROOM. |
| | |
| | 9.)PLEASE PROVIDE DETAILS FOR THE |
| | EXISTING ACCESSIBLE BATHROOM FBC11-4.22 |
| | SO THAT EXISTING CONDITIONS CAN BE |
| | REVIEWED FOR CODE COMPLIANCE. |
| | |
| | 10.) THE DESIGN CRITERIA PROVIDED SHEET |
| | A1 GENERAL NOTES #21 IS FOR HANDRAILS. |
| | PLEASE SEE FBC1608.2.2(1)THROUGH(4). |
| | |
| | 11.) HANDRAILS ARE TO EXTEND AT THE TOP |
| | AND BOTTOM FBC1007.5.5. |
| | |
| | 12.) SHOW COMPLIANCE WITH FBC1015.3 FOR |
| | THE OPENINGS ON THE STAIRRAIL. |
| | |
| | 13.)SHEET S1 DOES NOT HAVE ALL OF THE |
| | INFORMATION REQUIRED FOR THE TITLE |
| | BLOCK, FAC61G1-15. |
| | |
| | 14.)SHEET FP1 IS NOW MISSING FROM THE |
| | PLAN.SEE MINIMUM PLAN REVIEW CRITERIA |
| | FBC104.3.1.1(5). |
| | |
| | 15.)SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALC. |
| | |