Plan Review Notes
Plan Review Notes For Permit 04030910
Permit Number 04030910
Review Stop B
Sequence Number 2
Notes
Date Text
2005-04-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST, ITEM #1.
 PROVIDE THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT, FS481, FAC61G1-16.
  
 2.)THE OWNER ON THE APPLICATION
 DOESN'T MATCH OUR RECORDS.PLEASE
 PROVIDE A COPY OF THE DEED.THE NOC IS
 LACKING COMPLETE INFORMATION (LEGAL,
 OWNER ADDRESS) AND NEEDS TO BE RECORDED.
  
 3.)SEE PREVIOUS LIST, ITEM #4.
 PROVIDE A DETAIL FOR THE SPIRAL STAIR.
 FBC104.2.1, "SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL
 NOT BE CITED AS A WHOLE OR IN PART . . .
 AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION."THE DETAIL SHOULD INCLUDE
 DIRECTION, ALL DIMENSIONS, HANDRAIL
 INFORMATION TO SHOW COMPLIANCE WITH FBC
 1007.8.2.1.
  
 4.)SOME COMMENTS WERE ADDRESSED IN THE
 FORM OF A LETTER.THE PLANS SHOULD SHOW
 CODE COMPLIANCE.PLEASE INCORPORATE
 THESE COMMENTS AS A PART OF THE PLAN.
  
 5.)DECLARE THE BUILDING TYPE ON THE
 PLAN.THE TRANSMITTAL LETTER STATED
 THAT IT IS TYPE IV UNPROTECTED.TYPE IV
 CONSTRUCTION DOES NOT ALLOW COMBUSTIBLES
 FOR FLOOR OR BEARING WALLS, FBC606 AND
 FBC TABLE 600.THE 1 HOUR REQUIREMENT
 YOU REFER TO IS IN YOUR MEMO IS FOR TYPE
 IV 1 HR PROTECTED.COMBUSTIBLES ARE
 STILL NOT ALLOWED IN TYPE IV 1 HR
 PROTECTED.
  
 6.)THE TRANSMITTAL LETTER INDICATED
 THAT THE OCCUPANT LOAD WILL BE LESS THAN
 5 AND NOT OPEN TO THE PUBLIC, EXEMPTING
 THIS JOB FROM VERTICAL ACCESSIBILITY.
 PLEASE INDICATE THIS ON THE PLAN.
  
 7.)PLEASE SEE PRIOR REQUEST FOR
 EXITING INFORMATION.IT IS NOT CLEAR
 WHERE THE DOORS LABELLED "1" (A DOUBLE
 DOOR AT THE BASE OF THE STAIRS, A SINGLE
 DOOR NEXT TO THE SPIRAL STAIR) LEAD.DO
 THEY LEAD TO THE OUTSIDE OR TO OTHER
 INTERIOR SPACE?PLEASE EITHER PROVIDE A
 SITE PLAN OR MAKE A NOTE ON THE PLAN.
  
 8.)SEE PREVIOUS LIST, SECOND FLOOR
 BATHROOM TO BE ADAPTABLE,
 FBC11-4.1.3(11).THE EXCEPTION FOR
 VERTICAL ACCESSIBILITY DOES NOT WAIVE
 THE REQUIREMENT FOR ADAPTABILITY
 (ABILITY FOR FUTURE GRAB BARS IF
 NECESSARY) IN THE BATHROOM.
  
 9.)PLEASE PROVIDE DETAILS FOR THE
 EXISTING ACCESSIBLE BATHROOM FBC11-4.22
 SO THAT EXISTING CONDITIONS CAN BE
 REVIEWED FOR CODE COMPLIANCE.
  
 10.) THE DESIGN CRITERIA PROVIDED SHEET
 A1 GENERAL NOTES #21 IS FOR HANDRAILS.
 PLEASE SEE FBC1608.2.2(1)THROUGH(4).
  
 11.) HANDRAILS ARE TO EXTEND AT THE TOP
 AND BOTTOM FBC1007.5.5.
  
 12.) SHOW COMPLIANCE WITH FBC1015.3 FOR
 THE OPENINGS ON THE STAIRRAIL.
  
 13.)SHEET S1 DOES NOT HAVE ALL OF THE
 INFORMATION REQUIRED FOR THE TITLE
 BLOCK, FAC61G1-15.
  
 14.)SHEET FP1 IS NOW MISSING FROM THE
 PLAN.SEE MINIMUM PLAN REVIEW CRITERIA
 FBC104.3.1.1(5).
  
 15.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  