| 2005-02-14 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 BUILDING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) SHTS A0, A1, A2, S1 UNABLE TO READ |
| | THE INFORMATION FROM THE SEAL. RESEAL |
| | THE SHEETS TO IMPRESS THE INFORMATION ON |
| | THE SEALED SHEETS. FAC 61G1-16.001/.002 |
| | AND FS 481.2055. |
| | 2) ALL ARCHITECTURAL SHEETS, THE TITLE |
| | BLOCK MUST, AT A MINIMUM, CONTAIN THE |
| | FOLLOWING INFORMATION: |
| | 61G1-16.004(2) FIRM LICENSE NUMBER |
| | 61G1-16.004(6) PRINTED NAME OF THE |
| | PERSON SEALING THE DOCUMENT. |
| | FS 481.219 & 481.2055. |
| | 3) SHT FP-1 SHEET NOT SIGNED, SEALED, |
| | AND DATED. 61G1-16.003 & FS 481.2055. |
| | 4) SHT A1 DETAIL #1NO DEAD ENDS, |
| | SECTION 704.5. ALL DEMO'D PIPING SHALL |
| | NOT BE COVERED PRIOR TO INSPECTION. |
| | 5) SHT A1 DETAIL #2 SINK SHALL BE |
| | ACCESSIBLE. SUBMIT A DETAIL SHOWING |
| | COMPLIANCE WITH SECTION 11-4.24 AND ALL |
| | SUBSECTIONS. (FORWARD APPROACH REQUIRED) |
| | 6) SHT A1 DETAIL #3 TOILET ROOM SHALL BE |
| | ACCESSIBLE. SUBMIT A DETAIL SHOWING |
| | COMPLIANCE WITH SECTIONS 11-4.16, |
| | 11-4.19, & 11-4.22 AND ALL SUBSECTIONS. |
| | 7) SHT A2 ROOM FINISH. INDICATE WHAT |
| | "WD" IS FOR THE BASE AND SHOW COMPLIANCE |
| | WITH SECTION 1204.2 SURRONDING MATERIALS |
| | FOR THE BASE AND THE PAINTED WALLS. |
| | 8) SHT P-1 CLEANOUT IS REQUIRED AT THE |
| | JUNCTION OF THE BUILDING DRAIN AND THE |
| | BUILDING SEWER FOR THE NEW BUILDING |
| | DRAIN LINE FOR THE SINK AND THE 2ND |
| | FLOOR TOILET ROOM. SECTION 708.3.5. |
| | |
| | REVIEW BY KEN STEVENS |