| Plan Review Notes For Permit 04030910 |
| Permit Number |
04030910 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-02-07 00:00:00 | DENIED: | | | 1.PLAN SHEET A-1 INDICATES THE | | | FOLLOWING PARTITIONS ARE FIRE RATED; #3 | | | (1ST FLOOR CONFERENCE ROOM) & #5 OFFICE, | | | #4.FIRE DAMPERS ARE NOT INDICATED ON | | | THE MECHANICAL PLANS.PER 2001 FBC(M) | | | 607.6, LOCATION AND INSTALLATION DETAILS | | | FOR EACH FIRE DAMPER AND ACCESS DOOR | | | SHALL BE PROPERLY IDENTIFIED ON PLAN. | | | | | | 2.PLAN SHEET A3 INDICATES UL L501 | | | FLOOR/CEILING ASSEMBLY WITH A 1 HOUR | | | RATING.PLEASE CLARIFY PROTECTION OF | | | OPENINGS. | | | | | | 3.PLEASE PROVIDE OUTSIDE AIR | | | CALCULATIONS IN ACCORDANCW WITH 2001 | | | FBC(M) TABLE 403.3. | | | | | | 4.PROVIDE ENERGY CALCULATIONS PER | | | CHAPTER 13 FBC SUB-CHAPTER 4. | | | | | | 5.SEE COMMONTS BY ELECTRICAL & BUILING | | | FOR REQUIRE REQUIREMENTS FOR LICENSE | | | NUMBERS AND CERTIFICATE OF AUTNORIZATION | | | PER FS 481.219 & 471.023. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|