Plan Review Notes
Plan Review Notes For Permit 04030910
Permit Number 04030910
Review Stop B
Sequence Number 1
Notes
Date Text
2005-01-31 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PLEASE PROVIDE A LEGIBLE SEAL AND
 THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT, FS481, FAC61G1-16.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 3.)PROVIDE AREA CALCULATIONS
 (PROPOSED
 NEW 2ND FLOOR).
  
 3.)THE OWNER ON THE APPLICATION
 DOESN'T MATCH OUR RECORDS.
  
 4.)PROVIDE A DETAIL FOR THE SPIRAL
 STAIRS TO COMPLY WITH FBC1007.8.2.1.
  
 5.)DECLARE A BUILDING TYPE FOR THE
 EXISTING BUILDING, FBC CHAPTER 6; SHOW
 COMPLIANCE WITH FBC TABLE 500.NOTE
 THAT YOU ARE ADDING A STORY AS THE
 MEZZANINE DOES NOT COMPLY WITH
 FBC503.2.3.2 & 3.
  
 7.)PROVIDE EXITING (EGRESS)
 INFORMATION, FBC CHAPTER 10. NONE
 SHOWN,
 AND IT IS NOT CLEAR WHERE THE EXISTING
 DOORS LEAD TO.
  
 8.)FP1 DOES NOT SHOW SPRINKLERS ON
 THE
 SECOND FLOOR PLAN AND THE GROUND FLOOR
 PLAN (FP1).
  
 9.)ENERGY CALCS REQUIRED,
 FBC13-103.1.2.
  
 10.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 11.) DECLARE AN OCCUPANT LOAD FOR THE
 MEZZANINE.
  
 12.) HOW IS VERTICAL ACCESSIBILITY
 ADDRESSED?FBC11-4.1.3(5)
  
 13.) SECOND FLOOR BATHROOM TO BE
 ADAPTABLE, FBC11-4.1.3(11).
  
 14.) FIRST FLOOR BATHROOM TO BE
 COMPLIANT WITH FBC11-4.22, PROVIDE
 DETAILS.
  
 15.) THE STAIRRAIL (A2) SERVES AS A
 GUARDRAIL.GUARDRAILS ARE TO COMPLY
 WITH FBC1608.2.2(1) THROUGH (4).
  
 16.) THE HALL SINK/CABINET IS TO COMPLY
 WITH FBC11-4.24.PROVIDE A DETAIL.
  
 17.) THE TWO DOORS, 5 AND 1 ARE TO
 COMPLY WITH CHAPTER 11, FIGURE 26, TWO
 HINGED DOORS IN A SERIES.
  