Plan Review Notes
Plan Review Notes For Permit 04030886
Permit Number 04030886
Review Stop E
Sequence Number 2
Notes
Date Text
2004-05-03 00:00:00***********UNSAT **********
  
 PLEASE SEE NOTES FROM FIRST REVIEW.\
  
 1)NOTE: PLEASE PROVIDE ALL INFORMATION
 AS REQ'D UNDER NEC 225.31, 250.32
 RISER DIAGRAM/FEED ETC. 215.5
 PLEASE PROVIDE MIN CIRCUIT INFORMATION
 ON PANEL SCHEDULE. 210.12/ 210.52/210.11
 C3 ETC.
  
 2)NOTE: PLEASE SEE FS 481.221 A FULL/
 COMPLETE SIGNATURE IS REQ'D. INITIALS
 ARE NOT PERMITTED. PLEASE PROVIDE COPIES
 OF LICENSE/ DRIVERS LICENSE TO VERIFY
 LEGAL SIGNATURE.
  
 3)NOTE: PLEASE SEE ATTACHED COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  