Plan Review Notes For Permit 04030886
Permit Number 04030886
Review Stop P
Sequence Number 1
Notes
Date Text
2004-03-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 CITY CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) OUTSIDE SHOWER DRAIN NOT APPROVED.
 NO RAIN WATER CAN DRAIN TO SANITARY.
 2) SECTION 909.1 ONLY THE FIXTURES FROM
 THE BATHROOM GROUP SHALL DRAIN INTO THE
 WET VENT HORIZONTAL DRAIN OF THE BATH-
 ROOM FIXTURES. ALL OTHE FIXTURES SHALL
 CONNECT DOWNSTREAM OF THE WET VENT. SEE
 RED LINE CORRECTIONS ON SHT A-1.
 3) INITIALS NOT ACCEPTABLE ON SEAL. FULL
 SIGNATURE REQUIRED. 61G1-16.003 FAC, AND
 FS 481.2055
  