| Plan Review Notes For Permit 04030886 |
| Permit Number |
04030886 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-03-30 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | CITY CODE | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) OUTSIDE SHOWER DRAIN NOT APPROVED. | | | NO RAIN WATER CAN DRAIN TO SANITARY. | | | 2) SECTION 909.1 ONLY THE FIXTURES FROM | | | THE BATHROOM GROUP SHALL DRAIN INTO THE | | | WET VENT HORIZONTAL DRAIN OF THE BATH- | | | ROOM FIXTURES. ALL OTHE FIXTURES SHALL | | | CONNECT DOWNSTREAM OF THE WET VENT. SEE | | | RED LINE CORRECTIONS ON SHT A-1. | | | 3) INITIALS NOT ACCEPTABLE ON SEAL. FULL | | | SIGNATURE REQUIRED. 61G1-16.003 FAC, AND | | | FS 481.2055 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|