Plan Review Notes For Permit 04030886
Permit Number 04030886
Review Stop E
Sequence Number 1
Notes
Date Text
2004-03-29 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SHOW COMPLIANCE WITH 225.31,
 250.30, AND 250.32(D). DICONNECTING
 MEANS AND GROUNDING. 2002 NEC.
  
 PLEASE NOTE THAT THE ARCHITECTS
 SIGNATURE IS REQUIRED ON HIS/HER SEAL
 PER 61G116.003.INITIALS ARE NOT
 ACCEPTABLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW