2004-04-05 00:00:00BUILDING REVIEW CHECKLIST:
 1-REVISE ENERGY CALCULATIONS: NEED TO BE
 CALCULATED FOR WORST CASE SCENARIO IF
 IT'S TO BE USED AS TYPICAL FOR ALL
 HOUSES. OR PROVIDE ENERGY CALCULATIONS
 THAT ARE CALCULATED FOR EACH HOUSE
 ACCORDING TO THE ORIENTATION.
 2-PROVIDE FLORIDA PRODUCT APPROVAL AND
 DRAWINGS FOR ENTRY DOOR THAT MATCH TO
 EACH OTHER. EVERYTHING TO BE BENCHMARK
 OR THERMA TRU.
 3-PROVIDE FLORIDA PRODUCT APPROVAL COVER
 FOR SLIDING GLASS DOORS AND FIXED
 WINDOWS. AND PROVIDE ONLY THE DWGS FOR
 WINDOWS/DOORS TO BE INSTALLED IN THIS
 HOUSE.
 4-DETAIL E/4 AND RESIDENTIAL NOTES ON
 DWG #2 DON'T MATCH. CLARIFY SPACING
 OF FASTENERS.
 5-TYPICAL WALL SECTION A/4. SPECIFY
 WHERE ARE TABLES 6 AND 8 FOR ROOF TILE
 FASTENING TAKEN FROM/ SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 6-IMPACT FEES PAID RECEIPT NEED TO HAVE
 A PR NUMBER. CLARIFY WHY AMOUNT PAID
 IS LESS THAN AMOUNT STAMPED ON PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ