| 2004-04-05 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1-REVISE ENERGY CALCULATIONS: NEED TO BE | | | CALCULATED FOR WORST CASE SCENARIO IF | | | IT'S TO BE USED AS TYPICAL FOR ALL | | | HOUSES. OR PROVIDE ENERGY CALCULATIONS | | | THAT ARE CALCULATED FOR EACH HOUSE | | | ACCORDING TO THE ORIENTATION. | | | 2-PROVIDE FLORIDA PRODUCT APPROVAL AND | | | DRAWINGS FOR ENTRY DOOR THAT MATCH TO | | | EACH OTHER. EVERYTHING TO BE BENCHMARK | | | OR THERMA TRU. | | | 3-PROVIDE FLORIDA PRODUCT APPROVAL COVER | | | FOR SLIDING GLASS DOORS AND FIXED | | | WINDOWS. AND PROVIDE ONLY THE DWGS FOR | | | WINDOWS/DOORS TO BE INSTALLED IN THIS | | | HOUSE. | | | 4-DETAIL E/4 AND RESIDENTIAL NOTES ON | | | DWG #2 DON'T MATCH. CLARIFY SPACING | | | OF FASTENERS. | | | 5-TYPICAL WALL SECTION A/4. SPECIFY | | | WHERE ARE TABLES 6 AND 8 FOR ROOF TILE | | | FASTENING TAKEN FROM/ SEC. 104.2.1.2 | | | CITY AMENDMENTS TO FBC 2001. | | | 6-IMPACT FEES PAID RECEIPT NEED TO HAVE | | | A PR NUMBER. CLARIFY WHY AMOUNT PAID | | | IS LESS THAN AMOUNT STAMPED ON PLANS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ |
|