| 2004-04-15 00:00:00 | BUILDING REVIEW PROVISO: | | | 1-FLOOD ZONE AO. NEED TO PROVIDE THE | | | ELEVATION CERTIFICATE. | | | 2-DETAIL E/4 AND RESIDENTIAL NOTES ON | | | DWG #2 DON'T MATCH. CLARIFY ANCHOR | | | SPACING. SEC. 104.2.1.2 CITY | | | AMENDMENTS TO FBC 2001. | | | 3-TYPICAL WALL SECTION A/4: SPECIFY | | | WHERE ARE TABLES 6 AND 8 TAKEN FOR | | | ROOF TILE FASTENERS TAKEN FROM. | | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
|