| 2004-04-05 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-ENERGY CALCULATIONS ARE NOT CALCULATED |
| | FOR WORST CASE SCENARIO.THEY CAN'T BE |
| | SUBMITTED AS TYPICAL FOR THIS MODEL. |
| | PROVIDE ENERGY CALCULATIONS FOR WORST |
| | CASE SCENARIO OR PROVIDE ENERGY CALCS |
| | THAT ARE CALCULATED FOR EACH HOUSE |
| | ACCORDING TO THE ORIENTATION OF IT. |
| | 2-ENTRY DOOR PRODUCT APPROVAL: DRAWINGS |
| | DON'T MATCH PRODUCT APPROVAL. DRAWINGS |
| | ARE FOR "BENCHMARK" & PRODUCT APPROVAL |
| | COVER IS FOR "THERMA TRU" DOORS. |
| | 3-PROVIDE FLORIDA PRODUCT APPROVAL COVER |
| | PAGE FOR SLIDING GLASS DOORS AND FIXED |
| | WINDOWS. AND PROVIDE ONLY THE DWGS FOR |
| | WINDOWS AND DOORS TO BE INSTALLED IN |
| | THIS HOUSE. |
| | 4-DETAIL E/4 AND RESIDENTIAL NOTES ON |
| | DWG #2 DON'T MATCH. DETAIL E/4 CALLS |
| | FOR 6"O.C. SPACING, WHILE NOTES CALL |
| | FOR 16"O.C. REVISE AS REQUIRED. |
| | 5-TYPICAL WALL SECTION A/4. SPECIFY |
| | WHERE ARE TABLES 6 AND 8 FOR ROOF TILE |
| | FASTENING TAKEN FROM. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT 805-6712. |