Plan Review Notes
Plan Review Notes For Permit 04030734
Permit Number 04030734
Review Stop E
Sequence Number 2
Notes
Date Text
2004-05-04 00:00:00**** REDLINED PLANS***
  
 VERIFY OCP AND AWG FOR AHU'S, DO NOT
 SEEM TO CORRELATE W/ LOAD CALCS.
 PLEASE SEE 424.3B
  
 PLEASE SEE 250.66 FOR GEC, SHOWS #6??
  
 SD'S REQ'D INSIDE AND OUTSIDE RM, THIS
 IS AN ADAPTABLE SLEEPING RM.,
 NFPA-72 8-1
 PLEASE ALSO PROVIDE ARC FAULT PROTECTION
 PER 210.12
  
 ABOVER ITEMS REDLINED.