| Plan Review Notes For Permit 04030734 |
| Permit Number |
04030734 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-04-05 00:00:00 | DENIED | | | 1.SHOW WINDOW AND DOOR BUCK DETAIL. | | | BUCKS SHALL BE INSTALLED ACCORDING TO | | | FBC 1707.4.4.2UNLESS OTHERWISE TESTED, | | | BUCKS SHALL EXTEND BEYOND THE INTERIOR | | | FACE OF THE WINDOW OR DOOR FRAME SUCH | | | THAT FULL SUPPORT OF THE FRAME IS | | | PROVIDED. | | | | | | 2.SHOW DOOR RATING FOR DOOR #1. | | | | | | 3.SUBMIT ENERGY CALCULATIONS. | | | | | | 4.SHOW INTERIOR WALL FRAMING DETAIL | | | AT OLD GARAGE DOOR LOCATION AND ALSO | | | SHOW THICKNESS OF DRYWALL USED. | | | | | | ANY QUESTIONS CALL ME | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|