| Date |
Text |
| 2004-08-02 00:00:00 | ****CORRECTIONS**** |
| | REVISION; ADD COLUMNS 12-22 TO SCOPE |
| | OF WORK (ALREADY INCLUDED IN COST) |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)TO AVOID CONFUSION, RENUMBER THE |
| | PAGES.FOR INSTANCE, THERE SHOULD |
| | NOT BE TWO PAGE S1S, ONE SHOWING |
| | COLUMNS 1-11, ANOTHER SHOWING 12-22. |
| | |
| | 2.)ADDITIONAL PERMITS REQUIRED |
| | (MECHANICAL, ELECTRIC). |
| | |
| | 3.)SHOW COMPLIANCE WITH CHAPTER 11 |
| | (ACCESSIBILITY) FOR THE HABITABLE AREAS |
| | AND DECK INCLUDING ACCESSIBLE ENTRANCE |
| | (ELEVATION OF GRADE, ENTRY), DOOR |
| | WIDTHS, CLEAR FLOOR SPACE, ETC.PLANS |
| | SHOULD CLEARLY SHOW EITHER EXISTING |
| | CONDITIONS WHICH ARE CURRENTLY CODE |
| | COMPLIANT OR PROPOSED RENOVATIONS TO |
| | BRING INTO COMPLIANCE. |
| | |
| | 4.)THE CA NUMBER FOR THE ENGINEERING |
| | FIRM IS TO BE ON EACH SHEET, FAC61G15- |
| | 23.002. |
| | |
| | 5.)THE SHEETS SHOULD BE BOUND, NOT |
| | SUBMITTED LOOSE. |
| | |
| | 6.)THE INTERNAL PRESSURE COEFFICIENT |
| | PROVIDED ON THE LETTER FROM THE |
| | ENGINEER (PREVIOUS REVIEW WHEN PERMIT |
| | WAS ISSUED) IS NOT CORRECT FOR A |
| | PARTIALLY ENCLOSED BUILDING.PLEASE |
| | RESUBMIT AND MAKE CLEAR AS TO WHETHER |
| | THIS BUILDING WAS DESIGNED AS AN |
| | ENCLOSED OR PARTIALLY ENCLOSED BUILDING. |
| | |
| | 7.)SEE FBC3401.7.2.6 REGARDING |
| | OVER 50% REPAIRS TO EXISTING BUILDINGS. |
| | SHOW COMPLIANCE WITH FBC TABLE 500 AND |
| | FBC TABLE 600.DECLARE AN OCCUPANCY, |
| | BUILDING TYPE, NOTE WHETHER SPRINKLED |
| | OR NOT, SHOW COMPLIANCE WITH |
| | EGRESS REQUIREMENTS CHAPTER 10.NOTE |
| | OCCUPANCY SEPARATIONS FBC704 IF |
| | REQUIRED. |
| | |
| | 8.)THERE ARE OLD ELECTRIC AND FIRE |
| | REVIEWS IN THE COMPUTER; PLEASE SUBMIT |
| | THOSE APPROVED SHEETS.OTHERWISE NEW |
| | REVIEWS WILL BE REQUIRED. |