Plan Review Notes
Plan Review Notes For Permit 04030726
Permit Number 04030726
Review Stop B
Sequence Number 5
Notes
Date Text
2004-08-02 00:00:00****CORRECTIONS****
 REVISION; ADD COLUMNS 12-22 TO SCOPE
 OF WORK (ALREADY INCLUDED IN COST)
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)TO AVOID CONFUSION, RENUMBER THE
 PAGES.FOR INSTANCE, THERE SHOULD
 NOT BE TWO PAGE S1S, ONE SHOWING
 COLUMNS 1-11, ANOTHER SHOWING 12-22.
  
 2.)ADDITIONAL PERMITS REQUIRED
 (MECHANICAL, ELECTRIC).
  
 3.)SHOW COMPLIANCE WITH CHAPTER 11
 (ACCESSIBILITY) FOR THE HABITABLE AREAS
 AND DECK INCLUDING ACCESSIBLE ENTRANCE
 (ELEVATION OF GRADE, ENTRY), DOOR
 WIDTHS, CLEAR FLOOR SPACE, ETC.PLANS
 SHOULD CLEARLY SHOW EITHER EXISTING
 CONDITIONS WHICH ARE CURRENTLY CODE
 COMPLIANT OR PROPOSED RENOVATIONS TO
 BRING INTO COMPLIANCE.
  
 4.)THE CA NUMBER FOR THE ENGINEERING
 FIRM IS TO BE ON EACH SHEET, FAC61G15-
 23.002.
  
 5.)THE SHEETS SHOULD BE BOUND, NOT
 SUBMITTED LOOSE.
  
 6.)THE INTERNAL PRESSURE COEFFICIENT
 PROVIDED ON THE LETTER FROM THE
 ENGINEER (PREVIOUS REVIEW WHEN PERMIT
 WAS ISSUED) IS NOT CORRECT FOR A
 PARTIALLY ENCLOSED BUILDING.PLEASE
 RESUBMIT AND MAKE CLEAR AS TO WHETHER
 THIS BUILDING WAS DESIGNED AS AN
 ENCLOSED OR PARTIALLY ENCLOSED BUILDING.
  
 7.)SEE FBC3401.7.2.6 REGARDING
 OVER 50% REPAIRS TO EXISTING BUILDINGS.
 SHOW COMPLIANCE WITH FBC TABLE 500 AND
 FBC TABLE 600.DECLARE AN OCCUPANCY,
 BUILDING TYPE, NOTE WHETHER SPRINKLED
 OR NOT, SHOW COMPLIANCE WITH
 EGRESS REQUIREMENTS CHAPTER 10.NOTE
 OCCUPANCY SEPARATIONS FBC704 IF
 REQUIRED.
  
 8.)THERE ARE OLD ELECTRIC AND FIRE
 REVIEWS IN THE COMPUTER; PLEASE SUBMIT
 THOSE APPROVED SHEETS.OTHERWISE NEW
 REVIEWS WILL BE REQUIRED.