2004-07-12 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)REGARDING THE SITE SPECIFIC PRODUCT
 APPROVALS:
  
 A. CERTIFICATE OF INDEPENDENCE REQUIRED,
 FAC9B-72.040(5)(G) IN ACCORDANCE WITH
 FAC9B-72.110.
  
 B. FAC9B-72.070(4)(A) REQUIRES THE
 ADDRESS OF THE MANUFACTURER.
  
 C. THE TEST REPORT FOR THE ROOF SYSTEM
 IS TO BE SEALED.PROVIDE THE LICENSE
 NUMBER FOR THE PE FAC61G15-23.002
 (DONALD FLOOD, PE, TEST REPORT).
  
 D. THE SITE SPECIFIC PRODUCT APPROVALS
 SHOULD PROVIDE PRESSURE LIMITATIONS
 TO CORRELATE WITH THE PLANS.
  
 E.THE DOCUMENTATION WHICH HAS BEEN
 PREPARED BY OUT OF STATE ENGINEERS
 CANNOT BE SUBMITTED FOR PUBLIC RECORD.
 ENGINEERING MUST BE PREPARED BY A
 FLORIDA LICENSED ENGINEER.
  
 2.)PLEASE PROVIDE THE CERTIFICATE
 OF AUTHORIZATION NUMBER FOR THE
 ENGINEERING FIRM ON EACH SHEET AS
 REQUIRED BY FAC61G15-23.002.
  
 3.)WHERE HAVE THE DESIGN PRESSURES
 FOR WIND LOAD (S4) BEEN OBTAINED FROM?
  
 4.)THE ROOF SITE SPECIFIC PRODUCT
 APPROVAL MAKES REFERENCE TO DESIGN
 PRESSURES ON THE PLAN, SHEET S4, OF
 -37.7 AND -44.7, BUT THIS IS NOT
 CONSISTENT WITH THE PRESSURES SHOWN
 ON THAT SHEET.PLEASE CLARIFY.
  
 5.)PROVIDE THE ENCLOSURE
 CLASSIFICATION FBC1606.1.7(4) (2003
 AMENDMENT).IF THIS BUILDING IS
 DESIGNED AS AN ENCLOSED BUILDING,PROVIDE
 PRODUCT INFORMATION FOR THE DOORS AND
 LOUVERS THAT ARE BEING REINSTALLED.
  
 5.)WHEN RESUBMITTING, REPLACE ONLY
 SHEETS WHICH HAVE CHANGED.ALL SETS
 ARE TO BE BOUND (DO NOT SUBMIT LOOSE
 SHEETS).SUBMIT OLD SHEETS SEPARATELY
 FOR REFERENCE.
  
 6.)PROVIDE DESIGN PRESSURE REQUIREMENT
 FOR THE WALL PANELS, FBC1606.1.7(5).