| 2004-04-14 00:00:00 | DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE OVAL WINDOW IN THE MASTER BATH IS |
| | REQUIRED TO BE TEMPERED PER FBC 2405.2. |
| | |
| | 3) SPECIFY ON THE PLANS THAT THE DOOR |
| | FROM THE GARAGE TO THE CONDITIONED SPACE |
| | IS SOLID CORE OR INSULATED AS REQUIRED |
| | BY FBC 13-603. |
| | |
| | 4) SPECIFY THE ATTIC LIVE LOAD ON THE |
| | PLANS. SEE FBC TABLE 1604.1. |
| | |
| | 5) SPECIFY THE LENGTH/EMBED DEPTH OF THE |
| | 3/16" TAPCONS IN DETAIL 8 ON SHEET 8. |
| | |
| | 6) THE STORM PANEL INSTALLATION SCHEDULE |
| | AND KEY PLAN HAS SOME DISCREPANCIES WITH |
| | THE ARCHITECTURAL PLANS. PLEASE CORRECT. |
| | |
| | 7) THE TRUSS ANCHOR SCHEDULE LISTS A |
| | NUE-VUE NVSTA 48 CONNECTOR. THE STATE |
| | PRODUCT APPROVAL SUBMITTED IS FOR NVRT |
| | 12-48. |
| | |
| | 8) THE TRUSS ANCHOR SCHEDULE LISTS A |
| | SIMPSON HUC 412 CONNECTOR WITH 1505# OF |
| | UPLIFT. THE STATE PRODUCT APPROVAL |
| | SUBMITTED IS FOR A HU 412 WITH 905# OF |
| | UPLIFT. PLEASE CLARIFY. |
| | |
| | 9) THE SUBMITTAL FOR THE BUTT GLASS |
| | WINDOW IS INCOMPLETE AND HAS ERRORS. THE |
| | THIRD PARTY QUALITY ASSURANCE IS |
| | REQUIRED. THE LOT # ON SHEET 1 OF 2 IS |
| | INCORRECT. SPECIFY THE DESIGN PRESSURES. |
| | SPECIFY LIMITATIONS. SUBMIT CALULATIONS. |
| | SUBMIT SPECIFICATIONS FOR THE GE 1200 |
| | SILICONE. |
| | |
| | 10) SUBMIT STATE PRODUCT APPROVAL FOR |
| | THE COLLIER GARAGE DOOR WITH APPROVED |
| | STATUS AND FOR THE SMALL 8'X 7' GARAGE |
| | DOOR WHICH IS SMALLER THAN THE MINIMUM |
| | SIZE STATED ON THE PRODUCT APPROVAL |
| | DRAWINGS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |