Plan Review Notes
Plan Review Notes For Permit 04030653
Permit Number 04030653
Review Stop B
Sequence Number 1
Notes
Date Text
2004-04-14 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE OVAL WINDOW IN THE MASTER BATH IS
 REQUIRED TO BE TEMPERED PER FBC 2405.2.
  
 3) SPECIFY ON THE PLANS THAT THE DOOR
 FROM THE GARAGE TO THE CONDITIONED SPACE
 IS SOLID CORE OR INSULATED AS REQUIRED
 BY FBC 13-603.
  
 4) SPECIFY THE ATTIC LIVE LOAD ON THE
 PLANS. SEE FBC TABLE 1604.1.
  
 5) SPECIFY THE LENGTH/EMBED DEPTH OF THE
 3/16" TAPCONS IN DETAIL 8 ON SHEET 8.
  
 6) THE STORM PANEL INSTALLATION SCHEDULE
 AND KEY PLAN HAS SOME DISCREPANCIES WITH
 THE ARCHITECTURAL PLANS. PLEASE CORRECT.
  
 7) THE TRUSS ANCHOR SCHEDULE LISTS A
 NUE-VUE NVSTA 48 CONNECTOR. THE STATE
 PRODUCT APPROVAL SUBMITTED IS FOR NVRT
 12-48.
  
 8) THE TRUSS ANCHOR SCHEDULE LISTS A
 SIMPSON HUC 412 CONNECTOR WITH 1505# OF
 UPLIFT. THE STATE PRODUCT APPROVAL
 SUBMITTED IS FOR A HU 412 WITH 905# OF
 UPLIFT. PLEASE CLARIFY.
  
 9) THE SUBMITTAL FOR THE BUTT GLASS
 WINDOW IS INCOMPLETE AND HAS ERRORS. THE
 THIRD PARTY QUALITY ASSURANCE IS
 REQUIRED. THE LOT # ON SHEET 1 OF 2 IS
 INCORRECT. SPECIFY THE DESIGN PRESSURES.
 SPECIFY LIMITATIONS. SUBMIT CALULATIONS.
 SUBMIT SPECIFICATIONS FOR THE GE 1200
 SILICONE.
  
 10) SUBMIT STATE PRODUCT APPROVAL FOR
 THE COLLIER GARAGE DOOR WITH APPROVED
 STATUS AND FOR THE SMALL 8'X 7' GARAGE
 DOOR WHICH IS SMALLER THAN THE MINIMUM
 SIZE STATED ON THE PRODUCT APPROVAL
 DRAWINGS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714