| Plan Review Notes For Permit 04030630 |
| Permit Number |
04030630 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-03-27 00:00:00 | | | | THE POOL SPECIFICATIONS INDICATE NO POOL | | | HEATER, BUT THE CONTRACT SUBMITTED WITH | | | THE APPLICATION INDICATES THERE IS TO | | | BE A HEATER. SUBMIT LOAD CALCULATIONS | | | FOR THE ELECTRICAL SERVICE, INDICATE | | | SIZE OF EXISTING SERVICE, AND SHOW ALL | | | LOADS TO BE ADDED WITH THE SCOPE OF | | | THIS WORK. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|