| Plan Review Notes For Permit 04030626 |
| Permit Number |
04030626 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-03-16 00:00:00 | ***********DENIED*********************** | | | 1) NEW FIRE ALARM SYSTEMS SHALL BE UL | | | LISTED FOR CENTRAL STATION SERVICE. | | | | | | 2) ALL NEW FIRE ALARM SYSTEMS THAT | | | SUPERVISE FIRE SPRINKLER SYSTEMS SHALL | | | BE UL CERTIFICATED AND HAVE DOCUMENT | | | ATTESTING TO THIS CERTIFICATION PRIOR TO | | | APPROVAL OF THESE PLANS. | | | | | | 3) THE FIRE ALARM SYSTEM SHALL BE CLASS | | | "A" OR FULLY ADDRESSABLE. | | | | | | 4) ALL DUCT DETECTORS SHALL SEND AND PUT | | | THE SYSTEM IN GENERAL FIRE ALARM MODE IN | | | THE CITY OF WEST PALM BEACH NOT A | | | SUPERVISORY SIGNAL. | | | | | | THESE COMMENTS AND NOTES ARE FOR PERMITS | | | # 04030626 AND 04030625 | | | | | | NATE M | | | 805-6722 OR 835-2910 |
|