| 2004-04-14 00:00:00 | DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE FL PRODUCT APPROVAL #S LISTED FOR |
| | TWO OF THE FIXED GLASS WINDOWS IN THE |
| | SCHEDULE ON SHEET 3 ARE INCORRECT. |
| | |
| | 3) SPECIFY THE CONNECTORS AT THE BASE OF |
| | THE TWO 3-2X4 POSTS IN THE WALL BELOW |
| | THE GIRDER TRUSS AT MASTER SUITE. |
| | |
| | 4) SPECIFY THE ATTIC LIVE LOAD ON THE |
| | PLANS. SEE FBC TABLE 1604.1. |
| | |
| | 5) SUBMIT STATE PRODUCT APPROVAL FOR THE |
| | COLLIER GARAGE DOOR WITH APPROVED STATUS |
| | AND FOR THE 8'X 7' GARAGE DOOR WHICH IS |
| | SMALLER THAN THE MINIMUM SIZE ALLOWED BY |
| | THE PROD.APP. DRAWING. |
| | |
| | 6) THE TRUSS ANCHOR SCHEDULE ON SHEET 9 |
| | LISTS A NUE-VUE NVSTA 48 CONNECTOR. THE |
| | STATE PRODUCT APPROVAL SUBMITTED LISTS A |
| | NVRT 48 OR NVSTA 22. PLEASE CLARIFY. |
| | |
| | 7) THE TRUSS CONNECTOR SCHEDULE LISTS A |
| | SIMPSON HUC 412 CONNECTOR WITH 1505# OF |
| | UPLIFT. THE STATE PRODUCT APPROVAL IS |
| | FOR A HU 412 WITH 905# OF UPLIFT. PLEASE |
| | CLARIFY. |
| | |
| | 8) THE STORM PANEL INSTALLATION SCHEDULE |
| | AND KEY PLAN IS MISSING THE WINDOW IN |
| | BATH #2. PLEASE CORRECT. |
| | |
| | 9) THE SUBMITTAL FOR THE BUTT GLASS |
| | WINDOW IS INCOMPLETE AND HAS ERRORS. THE |
| | THIRD PARTY QUALITY ASSURANCE IS |
| | REQUIRED. SPECIFY THE DESIGN PRESSURES. |
| | LIST LIMITATIONS. SUBMIT CALCULATIONS. |
| | SUBMIT THE SPECIFICATIONS FOR THE GE |
| | 1200 SILICONE. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |