| Plan Review Notes For Permit 04030555 |
| Permit Number |
04030555 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-04-07 00:00:00 | DENIED: | | | 1.PLAN SHEET M-1 INDICATES CO SENSORS | | | CONTROLLING THE EXHAUST FANS.IS IT THE | | | INTENT THAT THE EXHAUST FANS WILL NOT | | | RUN CONTINUOUSLY? | | | | | | 2.INDICATE AT WHAT LEVEL (PPM) THE | | | CO SENSORS ARE SET TO ACTIVATE THE | | | EXHAUST FANS. | | | | | | 3.PLEASE CLARIFY RETURN AIR TO THE | | | RTU.WILL THESE UNITS BE CONTROLLED BY | | | A THERMOSTAT OR HUMIDISTAT? | | | | | | 4.PLEASE NOTE PER 2002 NFPA 90A | | | 4.3.7.1, AIR SHALL NOT BE RECIRCULATED | | | FROM ANY SPACE IN WHICH FLAMMABLE VAPORS | | | OR DUST ARE PRESENT IN QUANTITIES OR | | | CONCENTRATIONS THAT WOULD INTRODUCE A | | | HAZARDOUS CONDITION INTO THE RETURN AIR | | | SYSTEM.THIS IS ALSO ADDRESSED IN | | | 2001 FBC(M) 502.1. | | | | | | 6.SEE COMMMENT #3 FROM K. STEVENS | | | (PLUMBING). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|