2004-10-06 00:00:00PROVISO:
 CO SENSORS SHALL ACTIVATE FANS UPON
 DETECTION OF A CONSENTRATION RATE OF NOT
 GREATER THAN 25 PPM PER 2001 FBC(M)
 403.3.
  
 CO SENSORS TO BE TESTED FOR FINAL
 INSPECTION.
  
 PVC CONDENSTATE PIPE LOCATED ON THE
 ROOF SHALL HAVE PROTECTION FROM UV RAYS
 PER MANUFACTURER'S SPECIFICATIONS.