| Plan Review Notes For Permit 04030554 |
| Permit Number |
04030554 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2004-07-16 00:00:00 | PROVISO: | | | CO SENSORS SHALL ACTIVATE FANS UPON | | | DETECTION OF A CONSENTRATION RATE OF NOT | | | GREATER THAN 25 PPM PER 2001 FBC(M) | | | 403.3. | | | | | | CO SENORS TO BE TESTED FOR FINAL | | | INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|