Plan Review Notes
Plan Review Notes For Permit 04030554
Permit Number 04030554
Review Stop FIRE
Sequence Number 4
Notes
Date Text
2004-12-08 00:00:001) WHEN THE FIRE ALARM CONTROL UNIT,
 INCLUDING THE DAILER-COMMUNICATOR, IS
 REPLACED IN AN EXISTING SYSTEM, IT WILL
 BE TREATED AS A NEW SYSTEM.
  
 2) NEW FIRE ALARM SYSTEMS SHALL BE UL
 LISTED FOR CENTRAL STATION SERVICE.
  
 3) ALL NEW FIRE ALARM SYSTEMS THAT
 SUPERVISE FIRE SPRINKLER SYSTEMS SHALL
 BE UL CERTIFICATED AND HAVE DOCUMENTS
 ATTESTING TO THIS CERTIFICATION PRIOR
 TO
 FINAL APPROVAL OF THE FIRE ALARM
 SYSTEM.
  
 4) THE FIRE ALARM SYSTEM SHALL BE CLASS
 "A" OR FULLY ADDRESSSABLE.
  
 5) THE WEST PALM BEACH FIRE MARSHAL
 OFFICE REQUIRES SMOKE DUCT DETECTORS TO
 SEND A GENERAL FIRE ALARM NOT A
 SUPERVISORY.
  
 6) PLEASE PROVIDE CUT SHEETS FOR ALL NEW
 DEVICES AND EQUIPMENTS.
  
 7) ALL THESE CHANGES SHOULD BE
 SUBMITTED
 UNDER PERMIT 04090486 (FIRE ALARM
 PERMIT).
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722