Plan Review Notes
Plan Review Notes For Permit 04030554
Permit Number 04030554
Review Stop M
Sequence Number 3
Notes
Date Text
2004-05-28 00:00:00PROVISO:
 1. PROVIDE SUBMITTAL FOR TESTING OF THE
 CO SENSORS.PLEASE REVISE PLANS AND
 REMOVE COMMENT "CO SENSORS TO BE TESTED
 BY SMOKE BOMBS".REFERENCE MANUFACTURER
 INSTRUCTIONS FOR TESTING.CO SENSORS
 SHALL ACTIVATE FANS UPON DETECTION OF
 A CONSENTRATION RATE OF 25 PPM (MAXIMUM)
 PER 2001 FBC(M) 403.4.
  
 2. PROVIDE MANFACTURERS INSTALLATION
 INSTRUCTIONS FOR THE CONNECTION OF THE
 UNDERFLOOR EXHAUST SYSTEM TO THE 3"
 MUFFLER HOSE. PROVIDE DETAIL ON JOBSITE
 AT THE TIME OF INSPECTION.
  
 3.PLEASE NOTE PLANS FOR THE UNDERFLOOR
 EXHAUST ARE NOT SIGNED, SEALED & DATED
 BY THE ENGINEER AS REQUIRED PER FS
 471.05.PLEASE HAVE THE ENGINEER COMPLY
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.