| Plan Review Notes For Permit 04030554 |
| Permit Number |
04030554 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-05-28 00:00:00 | PROVISO: | | | 1. PROVIDE SUBMITTAL FOR TESTING OF THE | | | CO SENSORS.PLEASE REVISE PLANS AND | | | REMOVE COMMENT "CO SENSORS TO BE TESTED | | | BY SMOKE BOMBS".REFERENCE MANUFACTURER | | | INSTRUCTIONS FOR TESTING.CO SENSORS | | | SHALL ACTIVATE FANS UPON DETECTION OF | | | A CONSENTRATION RATE OF 25 PPM (MAXIMUM) | | | PER 2001 FBC(M) 403.4. | | | | | | 2. PROVIDE MANFACTURERS INSTALLATION | | | INSTRUCTIONS FOR THE CONNECTION OF THE | | | UNDERFLOOR EXHAUST SYSTEM TO THE 3" | | | MUFFLER HOSE. PROVIDE DETAIL ON JOBSITE | | | AT THE TIME OF INSPECTION. | | | | | | 3.PLEASE NOTE PLANS FOR THE UNDERFLOOR | | | EXHAUST ARE NOT SIGNED, SEALED & DATED | | | BY THE ENGINEER AS REQUIRED PER FS | | | 471.05.PLEASE HAVE THE ENGINEER COMPLY | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|