Plan Review Notes
Plan Review Notes For Permit 04030554
Permit Number 04030554
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2004-05-19 00:00:001) ELECTRONIC SWITCHES, CHAINS AND LOCKS
 WILL BE REQUIRED ON FIRE LINE BACKFLOW
 DEVICE.
  
 2) PLEASE DISPLAY EXIT ROUTE(S) FOR
 VEHICLE LIFTS 1-6.
  
 3) PLEASE INDICATE TESTING CRITERION
 FOR CO VENTILATION SYSTEM.
  
 4) THE NOTE ON PAGE M-4 INDICATES
 SMOKE BOMBS WILL BE USED TO TEST
 CARBON MONOXIDE SYSTEM. THESE NOTES
 DO NOTINDICATE HOW THE MONITORS
 THEMSELVES WILL BE TESTED. IT WOULD
 APPEAR THAT CALIBRATION GAS SHOULD BE
 USED TO ENSURE SET POINTS ON THE
 DETECTORS ARE PROPER. PLEASE ADVISE.
  
 5) WHY IS THE STORAGE YARD NOT FIRE
 SPRINKLER PROTECTED. IS THERE NOT
 MATERIALS STORED THERE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910