| Plan Review Notes For Permit 04030554 |
| Permit Number |
04030554 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-05-19 00:00:00 | 1) ELECTRONIC SWITCHES, CHAINS AND LOCKS | | | WILL BE REQUIRED ON FIRE LINE BACKFLOW | | | DEVICE. | | | | | | 2) PLEASE DISPLAY EXIT ROUTE(S) FOR | | | VEHICLE LIFTS 1-6. | | | | | | 3) PLEASE INDICATE TESTING CRITERION | | | FOR CO VENTILATION SYSTEM. | | | | | | 4) THE NOTE ON PAGE M-4 INDICATES | | | SMOKE BOMBS WILL BE USED TO TEST | | | CARBON MONOXIDE SYSTEM. THESE NOTES | | | DO NOTINDICATE HOW THE MONITORS | | | THEMSELVES WILL BE TESTED. IT WOULD | | | APPEAR THAT CALIBRATION GAS SHOULD BE | | | USED TO ENSURE SET POINTS ON THE | | | DETECTORS ARE PROPER. PLEASE ADVISE. | | | | | | 5) WHY IS THE STORAGE YARD NOT FIRE | | | SPRINKLER PROTECTED. IS THERE NOT | | | MATERIALS STORED THERE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|