Plan Review Notes
Plan Review Notes For Permit 04030554
Permit Number 04030554
Review Stop P
Sequence Number 1
Notes
Date Text
2004-03-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) CONTACT RODNEY COMPO ENVIRONMENTAL
 COMPLIANCE TO DETERMINE IF A SAND-WATER/
 OIL SEPARATOR WILL BE REQUIRED. WASTE
 ORD 2938-96. (561) 837-4074.
 2) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2
 3) SHT B.A-9.1 SHOWER STALL SHALL BE
 ACCESSIBLE PER SECTION 11-4.21 AND ALL
 SUBSECTIONS. PROVIDE A DETAIL.
 4) SHT R-01 CONDENSATE LINES. INDICATE
 MATERIAL BEING USED FOR CONDENSATE LINES
 IF PVC, SUPPORTS SHALL BE 4' O/C PER
 TABLE 308.5. ALSO PIPE SHALL BE PROTECT-
 ED FROM U.V. RAYS PER MANUF. INSTALLAT-
 ION INSTRUCTIONS.
 5) SHTS P-1 & P-3 INDICATE SLOPE OF PIPE
 FOR STORM SEWERS. MINIMUM 1/4" PER FOOT
 PER TABLE 1106.3. IS STORM LINES ARE
 TIED TOGETHER, SUBMIT A STORM SEWER DIA-
 GRAM INDICATING SEWER PIPE SIZES AND
 SLOPE OF PIPE AND INDICATE TERMINATION
 OF STORM SEWER.
 6) SHT P-6 WATER RISER DIAGRAM. WATER
 HAMMER ARRESTORS SHALL BE LOCATED AT ALL
 QUICK CLOSING VALVES PER SECTION 604.9.
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE
 NOT AT THE TOP OF DROPS. PDI-WH 201 AND
 MANUF. INSTALL. INSTRUCTIONS.
 7) SHT P-6 EWH DETAIL. P/T RELIEF VALVE
 SHALL TIE INTO THE TOP 6" OF THE WATER
 HEATER PER SECTION 504.5.1.
 8) CERTIFICATE OF AUTHORIZATION SHALL BE
 INDICATED ON EACH PLUMBING AND ELECTRIC-
 AL SHEET. MECHANICAL SHEETS ARE NOT
 SIGNED AND SEALED.
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]