Plan Review Notes
Plan Review Notes For Permit 04030554
Permit Number 04030554
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-03-12 00:00:001) PLEASE EXPLAIN ACCESS FOR NEW
 SERVICE SHOP. VARIOUS GATES AND FENCES
 ARE PRESENT ON THE SITE.
  
 2) ELECTRONIC SWITCHES, CHAIN AND LOCK
 REQUIRED ON FIRE LINE BACKFLOW DEVICE.
  
 3) FIRE AND PARAMEDICAL ACCESS TO THE
 SITE SHALL BE PROVIDED DURING
 DEMOLITION AND CONSTRUCTION ACTIVITIES.
  
 4) PLEASE PROVIDE MORE DETAILS ON
 PROPOSED STORAGE.
  
 5) PLEASE PROVIDE FURTHER DETAILS ON
 300 GAL POLY TANK.
  
 6) WHAT OPENING PROTECTIVE DEVICE IS
 PLANNED BETWEEN HALL 103 AND SERVICE
 SHOP 112.
  
 7) THERE APPEARS TO BE TOO MANY
 TABLES AND CHAIRS SHOWN IN LOUNGE 111.
  
 8) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 9) PLEASE EXPLAIN EXITING RATIONALE
 FROM OTHER AREAS BESIDES SERVICE SHOP.
 IT APPEARS THAT EXITING HAS TO ENTER
 VIA THE SERVICE SHOP.
  
 10) ADDITONAL EXIT SIGNS APPEAR TO BE
 NEEDED.
  
 11) ARE THERE ANY EMERGENCY LIGHTS
 PRESENT.
  
 12) ARE FIRE RESCUE VEHICLES EXPECTED
 TO PASS UNDERNEATH THE NEW METAL
 CANOPY.
  
 13) BUILDING ADDRESS REQUIRED. A
 MINIMUM OF 6" HIGH NUMBERS.
  
 14) DOOR SCHEDULE INDICATES NO LABEL
 DOORS.
  
 15) MORE DETAILS REQUIRED ON CARBON
 MONOXIDE EVACUATION SYSTEM THAT IS
 PLANNED FOR USE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910