| Date |
Text |
| 2004-03-12 00:00:00 | 1) PLEASE EXPLAIN ACCESS FOR NEW |
| | SERVICE SHOP. VARIOUS GATES AND FENCES |
| | ARE PRESENT ON THE SITE. |
| | |
| | 2) ELECTRONIC SWITCHES, CHAIN AND LOCK |
| | REQUIRED ON FIRE LINE BACKFLOW DEVICE. |
| | |
| | 3) FIRE AND PARAMEDICAL ACCESS TO THE |
| | SITE SHALL BE PROVIDED DURING |
| | DEMOLITION AND CONSTRUCTION ACTIVITIES. |
| | |
| | 4) PLEASE PROVIDE MORE DETAILS ON |
| | PROPOSED STORAGE. |
| | |
| | 5) PLEASE PROVIDE FURTHER DETAILS ON |
| | 300 GAL POLY TANK. |
| | |
| | 6) WHAT OPENING PROTECTIVE DEVICE IS |
| | PLANNED BETWEEN HALL 103 AND SERVICE |
| | SHOP 112. |
| | |
| | 7) THERE APPEARS TO BE TOO MANY |
| | TABLES AND CHAIRS SHOWN IN LOUNGE 111. |
| | |
| | 8) PLEASE INDICATE INTERIOR FINISH |
| | CLASSIFICATION FOR WALLS AND CEILINGS. |
| | |
| | 9) PLEASE EXPLAIN EXITING RATIONALE |
| | FROM OTHER AREAS BESIDES SERVICE SHOP. |
| | IT APPEARS THAT EXITING HAS TO ENTER |
| | VIA THE SERVICE SHOP. |
| | |
| | 10) ADDITONAL EXIT SIGNS APPEAR TO BE |
| | NEEDED. |
| | |
| | 11) ARE THERE ANY EMERGENCY LIGHTS |
| | PRESENT. |
| | |
| | 12) ARE FIRE RESCUE VEHICLES EXPECTED |
| | TO PASS UNDERNEATH THE NEW METAL |
| | CANOPY. |
| | |
| | 13) BUILDING ADDRESS REQUIRED. A |
| | MINIMUM OF 6" HIGH NUMBERS. |
| | |
| | 14) DOOR SCHEDULE INDICATES NO LABEL |
| | DOORS. |
| | |
| | 15) MORE DETAILS REQUIRED ON CARBON |
| | MONOXIDE EVACUATION SYSTEM THAT IS |
| | PLANNED FOR USE. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |