| 2004-04-14 00:00:00 | ************ UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SIGN PLANS WITH COMPLETE |
| | SIGNATURE AS REQ'D UNDER FS 471.025, |
| | FAC 61G15-23.002 |
| | PLEASE ALSO INCLUDE ALL LICENSE #'S ON |
| | TITLE BLOCK AS REQ'D UNDER FAC 61G15-23. |
| | 002. FS 471.023 (CA#) DATE ALSO MUST BE |
| | SIGNED AS ORIG. THESE ITEMS HAVE BEEN |
| | SENT TO US FROM THE FBPE'S IN OTHER |
| | CASES AND WILL EFFECT ALL PLANS. |
| | |
| | 2)NOTE: PLEASE INCLUDE EQUIPMENT GROUND- |
| | ING CONDUCTORS FOR ALL PANELS.250.122, |
| | 250.110,,, |
| | |
| | 3)NOTE: PLEASE SEE NOTE #1 E-6, MENTIONS |
| | 4-3 1/2" CONDUITS, YET SB PANEL SHOWS |
| | 4" CONDUITS, PLEASE CORRELATE. |
| | |
| | 4)NOTE: PLEASE LABEL AND IDENTIFY ALL |
| | PANELS/EQUIPMENT ON PLANS. |
| | PANELS SBF AND SBR. |
| | PLEASE SEE NOTE:4 ON E-2, MENTION 80A |
| | PANEL TO BE INSTALLED FOR TELE BOARD. |
| | THIS COULD NOT BE LOCATED ON RISER DIA- |
| | -GRAM OR ON A PANEL FEEDING THIS 80A |
| | SUB-PANEL? |
| | THERE IS A "PANEL TC" LOCATED ONPANEL- |
| | -BOARD SB, BUT IS ONLY A 60A FEED. |
| | IS THIS PANEL ANOTHER PANEL OR SAME? |
| | PLEASE CORRELATE RISER, PANEL SCHEDULES, |
| | SIZE ETC. |
| | |
| | 5)NOTE: PLEASE SEE ELECTRIC RISER KEY- |
| | -NOTES, #3, MENTIONS BOTH SB, SBM TO BE |
| | "MAIN LUGS ONLY". PLEASE ADJUST NOTE. |
| | PLEASE ALSO CORRELATE AIC RATINGS INDI- |
| | -CATED. SBM IS SHOWN AS 10,000. SB AND |
| | NOTES MENTIONS, 22K. |
| | |
| | 6)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-- |
| | -ING OF EM/EXT LTS. TO BE ON WITH LOCAL |
| | BRANCH CIRCUITS. |
| | |
| | 7)NOTE: PLEASE SEE THAT ALL CIRCUITING |
| | WILL BE REQ'D TO BE ON PLANS AND CORRE- |
| | -LATE WITH SUBMITTED PANEL SCHEDULE(S). |
| | IF PERTAING TO ONLY GFI'S IN BAYS, |
| | PLEASE CALL TO DICUSS A POSSIBLE NOTE/ |
| | PROVISO. THIS MAY RESULT IN A FUTURE |
| | REVISION AND FEES DUE AT THAT TIME. |
| | IF THIS NOT AN OPTION, PLEASE ADDRESS |
| | AS NOTED. |
| | |
| | 8)NOTE: PLEASE PROVIDE ROOM DESIGNATION |
| | ON ELECTRICAL PLANS. |
| | |
| | PLEASE SEE COMMENTS FROM OTHER REVIEWERS |
| | AS THEY MAY HAVE AN AFFECT ON ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |