| 2004-04-15 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04030554 |
| | ADD: 2901 OKEECHOBEE BLVD |
| | CONT: ROEPNACK |
| | TEL: (561)444-2995 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) COMMENTS FROM THE FOUNDATION PERMIT |
| | (04030555) 1-8. |
| | 2) PLANS INDICATE VARIOUS PRE-ENGINEERED |
| | CANOPIES, PROVIDE INFORMATION ON THESE |
| | CANOPIES TO BE CONSIDERED UNDER THIS |
| | PERMIT. NOTE ON THE FOUNDATION PAGE , |
| | FOUNDATION SUBJECT TO CHANGE PENDING THE |
| | REVIEW. IF ENGINEER TO CHANGE CANOPY |
| | FOUNDATION, WOULD IT NOT MAKE SENSE TO |
| | HAVE THIS INFORMATION BEFORE HAND? |
| | 3) PLANS INDICATE A CANOPY ENCLOSED BY |
| | A FENCE. SHEET BA-1.2 INDICATES A |
| | 300 GAL POLY TANK AND (6) 500 GAL TANKS. |
| | WHAT TYPE OF LIQUIDS ARE TO BE HOUSED IN |
| | THESE TANKS? IS THIS A HAZARDOUS OCCUPAN |
| | CY? DOES THIS AREA REQUIRE A SECONDARY |
| | CONTAINMENT? THIS AREA TO BE FIRE SPRINK |
| | LERED? AGAIN NO PLANS SUBMITTED FOR |
| | CANOPY OR AWNING? |
| | 4) SHEET# S1.0 NOTE# 8, PRECAST COLUMNS |
| | ARE TO BE FASTENED TO THE FOUNDATION? |
| | HOW WILL THIS HAPPEN, THIS INFORMATION |
| | WILL ALSO BE NEEDED FOR THE FOUNDATION |
| | PERMIT. WILL THERE BE EMBEDS, ETC? |
| | LOCATIONS? |
| | 5) SHEET S1.1 DETAIL# 3, PLANS INDICATE |
| | A BEAM AT THE C-1 COLUMN AND SPANING |
| | INTO THE PRECAST COLUMNS, HOW WILL THIS |
| | OCCUR? WILL THE CENTER OF THE PRECAST |
| | COLUMN BE VOID FOR THIS BEAM? |
| | 6) THIS SAME SHEET DOES NOT INFORMATION |
| | AS TO WHAT TYPE OF BEAM TO BE USED AT |
| | THE WINDOWS OF THE LOUNGE, SHOP FOREMANS |
| | WINDOW, HALL OR OTHER OPENINGS IN THE |
| | BLOCK WALLS?IN SOME CASES THESE OPENINGS |
| | WILL ABUT AGAINST PRECAST COLUMNS? THE |
| | EAST WALL WHERE THE LOUVER IS LOCATED |
| | NO MENTION OF HOW TO HANDLE THIS, OR |
| | HEIGHT OF OPENING? |
| | 7) SHEET S.0 DETAIL# 7, HOW DOES THE |
| | VERTICAL BARS ATTACH TO THE SPANDREL |
| | BEAM? |
| | 8) SHEET M-2 LOUVER EAST WALL WITHIN |
| | 15'-0" OF THE PROPERTY LINE, REQUIRES |
| | OPENING PROTECTIVES, 705.1.1.2. |
| | 9) INDICATE HOW THE RTU ARE TO BE FASTEN |
| | ED TO THE ROOF DECK? |
| | 10)1606.1.4(1) IN WIND BORNE DEBRIS |
| | REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| | ASSUMED TO BE OPENINGS UNLESS SUCH |
| | GLAZING IS IMPACT RESISTANT OR PROTECTED |
| | WITH AN IMPACT RESISTANT COVERING MEET- |
| | ING THE REQUIREMENTS OF SSTD 12, ASTM |
| | E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| | 1) GLAZED OPENINGS LOCATED WITHIN 30 FT |
| | OF GRADE SHALL MEET THE REQUIREMENTS OF |
| | LARGE MISSLE TEST. |
| | 11) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | 12)FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WINDOWS |
| | B) SWING DOORS |
| | C) OVERHEAD DOORS |
| | D) EXTERIOR LOUVERS |
| | E) ROOFING ASSEMBLIES |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |