2004-04-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04030554
 ADD: 2901 OKEECHOBEE BLVD
 CONT: ROEPNACK
 TEL: (561)444-2995
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) COMMENTS FROM THE FOUNDATION PERMIT
 (04030555) 1-8.
 2) PLANS INDICATE VARIOUS PRE-ENGINEERED
 CANOPIES, PROVIDE INFORMATION ON THESE
 CANOPIES TO BE CONSIDERED UNDER THIS
 PERMIT. NOTE ON THE FOUNDATION PAGE ,
 FOUNDATION SUBJECT TO CHANGE PENDING THE
 REVIEW. IF ENGINEER TO CHANGE CANOPY
 FOUNDATION, WOULD IT NOT MAKE SENSE TO
 HAVE THIS INFORMATION BEFORE HAND?
 3) PLANS INDICATE A CANOPY ENCLOSED BY
 A FENCE. SHEET BA-1.2 INDICATES A
 300 GAL POLY TANK AND (6) 500 GAL TANKS.
 WHAT TYPE OF LIQUIDS ARE TO BE HOUSED IN
 THESE TANKS? IS THIS A HAZARDOUS OCCUPAN
 CY? DOES THIS AREA REQUIRE A SECONDARY
 CONTAINMENT? THIS AREA TO BE FIRE SPRINK
 LERED? AGAIN NO PLANS SUBMITTED FOR
 CANOPY OR AWNING?
 4) SHEET# S1.0 NOTE# 8, PRECAST COLUMNS
 ARE TO BE FASTENED TO THE FOUNDATION?
 HOW WILL THIS HAPPEN, THIS INFORMATION
 WILL ALSO BE NEEDED FOR THE FOUNDATION
 PERMIT. WILL THERE BE EMBEDS, ETC?
 LOCATIONS?
 5) SHEET S1.1 DETAIL# 3, PLANS INDICATE
 A BEAM AT THE C-1 COLUMN AND SPANING
 INTO THE PRECAST COLUMNS, HOW WILL THIS
 OCCUR? WILL THE CENTER OF THE PRECAST
 COLUMN BE VOID FOR THIS BEAM?
 6) THIS SAME SHEET DOES NOT INFORMATION
 AS TO WHAT TYPE OF BEAM TO BE USED AT
 THE WINDOWS OF THE LOUNGE, SHOP FOREMANS
 WINDOW, HALL OR OTHER OPENINGS IN THE
 BLOCK WALLS?IN SOME CASES THESE OPENINGS
 WILL ABUT AGAINST PRECAST COLUMNS? THE
 EAST WALL WHERE THE LOUVER IS LOCATED
 NO MENTION OF HOW TO HANDLE THIS, OR
 HEIGHT OF OPENING?
 7) SHEET S.0 DETAIL# 7, HOW DOES THE
 VERTICAL BARS ATTACH TO THE SPANDREL
 BEAM?
 8) SHEET M-2 LOUVER EAST WALL WITHIN
 15'-0" OF THE PROPERTY LINE, REQUIRES
 OPENING PROTECTIVES, 705.1.1.2.
 9) INDICATE HOW THE RTU ARE TO BE FASTEN
 ED TO THE ROOF DECK?
 10)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
 11) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 12)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) SWING DOORS
 C) OVERHEAD DOORS
 D) EXTERIOR LOUVERS
 E) ROOFING ASSEMBLIES
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026