Plan Review Notes
Plan Review Notes For Permit 04030532
Permit Number 04030532
Review Stop B
Sequence Number 6
Notes
Date Text
2007-04-06 10:15:08 
 DENIED
  
 1) CASEMENT SIZES ON DRAWINGS FOR OPENING 16,17AND 38
 EXCEED THE MAX. WIDTH FOR A SINGLE CASEMENT IN THE
 NOA, ALSO SPECIFY THE GLASS TYPE THAT WILL BE USED AS
 SOME DO NOT MEET YOUR DESIGN PRESSURES ON THE
 DRAWINGS.
  
 2) FIXED UNITS WILL ONLY MEET DESIGN PRESSURES IF GLASS
 TYPE B & D ARE USED PLEASE SPECFIY GLASS TYPE ON
 SUBMITTAL.
  
 3) VERIFY MULLION SIZE AND THICKNESS AS NOT ALL WILL
 WORK WITH THE DESIGN PRESSURES ON DRAWINGS.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716