| Plan Review Notes For Permit 04030532 |
| Permit Number |
04030532 |
|
| Review Stop |
B |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2007-04-06 10:15:08 | | | | DENIED | | | | | | 1) CASEMENT SIZES ON DRAWINGS FOR OPENING 16,17AND 38 | | | EXCEED THE MAX. WIDTH FOR A SINGLE CASEMENT IN THE | | | NOA, ALSO SPECIFY THE GLASS TYPE THAT WILL BE USED AS | | | SOME DO NOT MEET YOUR DESIGN PRESSURES ON THE | | | DRAWINGS. | | | | | | 2) FIXED UNITS WILL ONLY MEET DESIGN PRESSURES IF GLASS | | | TYPE B & D ARE USED PLEASE SPECFIY GLASS TYPE ON | | | SUBMITTAL. | | | | | | 3) VERIFY MULLION SIZE AND THICKNESS AS NOT ALL WILL | | | WORK WITH THE DESIGN PRESSURES ON DRAWINGS. | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|