| Plan Review Notes For Permit 04030532 |
| Permit Number |
04030532 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-11-30 10:26:29 | PLAN REVIEW UNDER THE 2001 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2003 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | MECHANICAL REVISION | | | *** DENIED *** | | | | | | 1) NEED TO SHOW THE SIZES OF THE SUPPLY AIR TRUNK LINE | | | AND ONE RETURN AIR DUCT ON THE SECOND FLOOR (SEE YELLOW | | | HIGH LIGHT ON MECHANICAL PLAN. | | | | | | 2) NEED TO SHOW THE CFM'S AT ALL SUPPLY AIR GRILLS ON | | | SECOND AND THIRD FLOORS. | | | | | | 3) NEED TO ADD AN EQUIPMENT LISTING TO THE MECHANICAL | | | PLAN SHOWING EQUIPMENT BEING INSTALLED AND ALL | | | PERTINENT INFORMATION. | | | | | | 4) THE MECHANICAL PLANS NEED THE PRINTED NAME AND | | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN ON | | | THEM. | | | | | | 5) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|