Plan Review Notes
Plan Review Notes For Permit 04030532
Permit Number 04030532
Review Stop M
Sequence Number 4
Notes
Date Text
2007-11-30 10:26:29PLAN REVIEW UNDER THE 2001 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2003 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION
 *** DENIED ***
  
 1) NEED TO SHOW THE SIZES OF THE SUPPLY AIR TRUNK LINE
 AND ONE RETURN AIR DUCT ON THE SECOND FLOOR (SEE YELLOW
 HIGH LIGHT ON MECHANICAL PLAN.
  
 2) NEED TO SHOW THE CFM'S AT ALL SUPPLY AIR GRILLS ON
 SECOND AND THIRD FLOORS.
  
 3) NEED TO ADD AN EQUIPMENT LISTING TO THE MECHANICAL
 PLAN SHOWING EQUIPMENT BEING INSTALLED AND ALL
 PERTINENT INFORMATION.
  
 4) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN ON
 THEM.
  
 5) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]