| 2008-08-11 16:48:39 | PLUMBING PLAN REVIEW: |
| | REVISION DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2001 FLORIDA BUILDING CODES WITH |
| | REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. PLEASE |
| | KNOW THAT THIS IS A REVISION NOT A SUBMITTAL AND A FEE |
| | OF $60.00 IS DUE FOR THIS REVISION PLAN REVIEW AND WILL |
| | NEED TO BE PAID FOR AS WELL AS THE CORRECTIONS TO THIS |
| | REVISION PRIOR OF THE NEXT REVISION SUBMITTED FOR PLAN |
| | REVIEW. |
| | |
| | 1. INFORMATION IS MISSING FROM THE TITLE BLOCK. |
| | PRINTED NAME AND LICENSE NUMBER OF THE PERSON SIGNING |
| | AND SEALING PLAN SHEETS AS WELL AS THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE FIRM IS MISSING FROM PLAN |
| | SHEETS. PER CHAPTER 481 AND FAC 61G1-16.004 TITLE |
| | BLOCK. |
| | |
| | 2. THE SUBMITTED RISER DIAGRAM FOR THE SECOND AND |
| | THIRD FLOOR ROOF DRAINS REQUIRES MORE INFORMATION. |
| | PLEASE PROVIDE A ROOF PLAN THAT INDICATES HOW THE ROOF |
| | OR DECK WILL BE PITCHED TO PROPERLY DRAIN, AND INDICATE |
| | THE FOLLOWING INFORMATION PER THE FOLLOWING CODE |
| | REFERENCES. |
| | A} DETAIL OF ROOF INDICATING SQUARE FOOTAGE OF ROOF |
| | AND VERTICAL WALLS (PARAPHET) DRAINING TO DOWNSPOUTS |
| | AND SCUPPERS TO VERIFY COMPLIANCE WITH FBC-2001 |
| | PLUMBING, SECTION 1101.1 SCOPE. |
| | B} VERTICAL CONDUCTORS AND LEADERS, PER FBC-2001 |
| | PLUMBING, SECTION 1106.2. |
| | C} VERTICAL WALLS, PER FBC-2001 PLUMBING, SECTION |
| | 1106.4. |
| | D} SCUPPERS, (PROVIDE DETAIL PER FBC-2001 BUILDING, |
| | SECTIONS 1503.4.2) SIZE PER FBC-2004 PLUMBING, SECTION |
| | 1107. |
| | E} SECONDARY (EMERGENCY) ROOF DRAINS, PER FBC-2001 |
| | PLUMBING, SECTION 1107. |
| | A) SECONDARY DRAINAGE REQUIRED, PER FBC-2001 PLUMBING, |
| | SECTION 1107.1. |
| | B) SEPERATE SYSTEMS REQUIRED PER FBC-2001 PLUMBING, |
| | SECTION 1107.2. |
| | C) SIZING OF SECONDARY DRAINS, PER FBC-2001 PLUMBING, |
| | SECTION 1107.3 |
| | F) PROTECTION AGAINST DECAY AND TERMITES, PER FBC-2001 |
| | BUILDING, SECTION 1504.4 (SHALL DISCHARGE A MINIMUM OF |
| | 1 FOOT AWAY FROM STRUCTURE). |
| | |
| | 3. PLEASE CLARIFY IF THESE ROOF DRAINS ARE FOR THE |
| | BALCONY AREA INDICATED ON SHEET 07 AND THE POOL DECK |
| | AREA ON SHEET 08. PLEASE KNOW THAT IF THIS IS THE |
| | LOCATION FOR THESE ROOF DRAINS THAT THE SUBMITTED DRAIN |
| | SPECIFICATION SHEET IS NOT COMPLIANT FOR A FLAT DECK. |
| | PER 1105.2 FLAT DECKS. STRAINERS FOR A FLAT SURFACE |
| | SHALL NOT BE LESS THAN TWO TIMES THE AREA OF THE |
| | CONDUCTOR OR LEADER TO WHICH THE DRAIN IS CONNECTED. |
| | SUBMITTED PLANS ARE INDICATING A 3 INCH LEADER.NOTE: |
| | PER FLAT DECK STRAINER CALCULATIONS FOR A 3 INCH LEADER |
| | (DIAMETER SQUARED TIMES .7854 OR 3 X 3 X .7854 = |
| | 14.1372) A 14.1372 INCH FLAT STRAINER IS REQUIRED. |
| | DRAIN SUBMITTED IS LESS THAN 10 INCH. |
| | |
| | 4. PROVIDE A DETAIL ON HOW THE ROOF DRAIN OR FLAT DECK |
| | DRAIN WILL BE INSTALLED PER THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. PER FBC-2001 PLUMBING |
| | SECTION 1101.1 SCOPE. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |