2008-08-11 16:48:39PLUMBING PLAN REVIEW:
 REVISION DENIED:
  
 PLAN REVIEW UNDER THE 2001 FLORIDA BUILDING CODES WITH
 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. PLEASE
 KNOW THAT THIS IS A REVISION NOT A SUBMITTAL AND A FEE
 OF $60.00 IS DUE FOR THIS REVISION PLAN REVIEW AND WILL
 NEED TO BE PAID FOR AS WELL AS THE CORRECTIONS TO THIS
 REVISION PRIOR OF THE NEXT REVISION SUBMITTED FOR PLAN
 REVIEW.
  
 1. INFORMATION IS MISSING FROM THE TITLE BLOCK.
 PRINTED NAME AND LICENSE NUMBER OF THE PERSON SIGNING
 AND SEALING PLAN SHEETS AS WELL AS THE CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE FIRM IS MISSING FROM PLAN
 SHEETS. PER CHAPTER 481 AND FAC 61G1-16.004 TITLE
 BLOCK.
  
 2. THE SUBMITTED RISER DIAGRAM FOR THE SECOND AND
 THIRD FLOOR ROOF DRAINS REQUIRES MORE INFORMATION.
 PLEASE PROVIDE A ROOF PLAN THAT INDICATES HOW THE ROOF
 OR DECK WILL BE PITCHED TO PROPERLY DRAIN, AND INDICATE
 THE FOLLOWING INFORMATION PER THE FOLLOWING CODE
 REFERENCES.
 A} DETAIL OF ROOF INDICATING SQUARE FOOTAGE OF ROOF
 AND VERTICAL WALLS (PARAPHET) DRAINING TO DOWNSPOUTS
 AND SCUPPERS TO VERIFY COMPLIANCE WITH FBC-2001
 PLUMBING, SECTION 1101.1 SCOPE.
 B} VERTICAL CONDUCTORS AND LEADERS, PER FBC-2001
 PLUMBING, SECTION 1106.2.
 C} VERTICAL WALLS, PER FBC-2001 PLUMBING, SECTION
 1106.4.
 D} SCUPPERS, (PROVIDE DETAIL PER FBC-2001 BUILDING,
 SECTIONS 1503.4.2) SIZE PER FBC-2004 PLUMBING, SECTION
 1107.
 E} SECONDARY (EMERGENCY) ROOF DRAINS, PER FBC-2001
 PLUMBING, SECTION 1107.
 A) SECONDARY DRAINAGE REQUIRED, PER FBC-2001 PLUMBING,
 SECTION 1107.1.
 B) SEPERATE SYSTEMS REQUIRED PER FBC-2001 PLUMBING,
 SECTION 1107.2.
 C) SIZING OF SECONDARY DRAINS, PER FBC-2001 PLUMBING,
 SECTION 1107.3
 F) PROTECTION AGAINST DECAY AND TERMITES, PER FBC-2001
 BUILDING, SECTION 1504.4 (SHALL DISCHARGE A MINIMUM OF
 1 FOOT AWAY FROM STRUCTURE).
  
 3. PLEASE CLARIFY IF THESE ROOF DRAINS ARE FOR THE
 BALCONY AREA INDICATED ON SHEET 07 AND THE POOL DECK
 AREA ON SHEET 08. PLEASE KNOW THAT IF THIS IS THE
 LOCATION FOR THESE ROOF DRAINS THAT THE SUBMITTED DRAIN
 SPECIFICATION SHEET IS NOT COMPLIANT FOR A FLAT DECK.
 PER 1105.2 FLAT DECKS. STRAINERS FOR A FLAT SURFACE
 SHALL NOT BE LESS THAN TWO TIMES THE AREA OF THE
 CONDUCTOR OR LEADER TO WHICH THE DRAIN IS CONNECTED.
 SUBMITTED PLANS ARE INDICATING A 3 INCH LEADER.NOTE:
 PER FLAT DECK STRAINER CALCULATIONS FOR A 3 INCH LEADER
 (DIAMETER SQUARED TIMES .7854 OR 3 X 3 X .7854 =
 14.1372) A 14.1372 INCH FLAT STRAINER IS REQUIRED.
 DRAIN SUBMITTED IS LESS THAN 10 INCH.
  
 4. PROVIDE A DETAIL ON HOW THE ROOF DRAIN OR FLAT DECK
 DRAIN WILL BE INSTALLED PER THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. PER FBC-2001 PLUMBING
 SECTION 1101.1 SCOPE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  