| 2004-06-08 00:00:00 | PROVISO |
| | ~~~~~~~ |
| | 1} PLEASE SEE MISSING RECEPTACLES |
| | FRONT AND/OR REAR OF DWELLING PER |
| | 210.52(E).THE ONES THAT WERE ADDED TO |
| | THE RESUB SET ARE HAND DRAWN. CHANGES |
| | MUST BE MADE MY THE ARCHITECT OF RECORD |
| | PER 61G1-16.003 FAC.* |
| | |
| | 2} PLEASE SEE MISSING RECEPT REQUIRED |
| | FOR A/C EQUIPMENT. 210.63. AGAIN RESUB |
| | CORRECTION WAS HAND DRAWN, SEE PREVIOUS |
| | NOTE.* |
| | |
| | 3} INDICATE COMPLIANCE WITH 225.31 & |
| | 250.32 AT THE STORAGE BUILDING.* |
| | |
| | 4} THE RESUBMITTED PLANS ARE STILL NOT |
| | IN COMPLIANCE WITH 8-1.4.1.6.2 NFPA-72. |
| | THE DETECTORS MUST BE LOCATED "IN" ALL |
| | SLEEPING ROOMS. ALSO ON EACH ADDITIONAL |
| | STORY,THAT WOULD INCLUDE THE 3RD FLOOR.* |
| | |
| | 5} MANY OF THE APPLIANCES THAT WERE |
| | LISTED IN THE ORIGINAL CALC'S HAVE BEEN |
| | DELETED FROM THE RESUB SET. PLEASE NOTE |
| | THAT IF THESE ARE ADDED BACK LATER A |
| | REVISED LOAD CALCULATION MUST BE |
| | RESUBMITTED AS A REVISION. PLEASE CHECK |
| | THE NUMBERS TO INSURE THE SERVICE WILL |
| | BE SUFFICIENT. THE ITEMS LEFT OFF TOTAL |
| | 19480 WATTS. ALSO THE WATER HEATER |
| | APPEARS TO BE UNDERSIZED FOR THE SIZE |
| | OF THE RESIDENCE. |
| | |
| | 6} THE RATINGS OF THE A/C EQUIPMENT ON |
| | THE ELECTRICAL CALC AND THE MECHANICAL |
| | SHEETS DO NOT CORRESPOND. IF THE |
| | MECHANICAL SHEETS ARE CORRECT THERE IS |
| | A 10 KW ERROR IN THE LOAD CALC'S.PLEASE |
| | CORRELATE THE INFORMATION. CHECK THE |
| | CALC'S! |
| | |
| | 7} PLEASE REMOVE THE #2 GND CONUCTOR |
| | FROM THE METER TO THE MAIN DISCONNECTS |
| | PER 250.4(B). IT CREATES A PARALLEL |
| | GROUND PATH. |
| | |
| | 8} RECEPTACLES NEED TO BE ADDED IN BED |
| | ROOMS #2 & 3 TO COMPLY WITH 210.52. |
| | |
| | 9} THE DISCONNECTS AT THE CONDENSING |
| | UNITS DO NOT APPEAR TO COMPLY WITH |
| | 110.26. |
| | |
| | 10} THE DATE THE PLANS WERE SEALED MUST |
| | BE ON THE TITLE BLOCK.61G-16.004(4).* |
| | |
| | NOTE: THE COMMENTS FOLLOWED BY AN |
| | ASTERISK WERE ON THE PREVIOUS REVIEW. |
| | SEE FS. 553.80(2)(B), ATTACHED. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |