Plan Review Notes
Plan Review Notes For Permit 04030532
Permit Number 04030532
Review Stop E
Sequence Number 2
Notes
Date Text
2004-06-08 00:00:00PROVISO
 ~~~~~~~
 1} PLEASE SEE MISSING RECEPTACLES
 FRONT AND/OR REAR OF DWELLING PER
 210.52(E).THE ONES THAT WERE ADDED TO
 THE RESUB SET ARE HAND DRAWN. CHANGES
 MUST BE MADE MY THE ARCHITECT OF RECORD
 PER 61G1-16.003 FAC.*
  
 2} PLEASE SEE MISSING RECEPT REQUIRED
 FOR A/C EQUIPMENT. 210.63. AGAIN RESUB
 CORRECTION WAS HAND DRAWN, SEE PREVIOUS
 NOTE.*
  
 3} INDICATE COMPLIANCE WITH 225.31 &
 250.32 AT THE STORAGE BUILDING.*
  
 4} THE RESUBMITTED PLANS ARE STILL NOT
 IN COMPLIANCE WITH 8-1.4.1.6.2 NFPA-72.
 THE DETECTORS MUST BE LOCATED "IN" ALL
 SLEEPING ROOMS. ALSO ON EACH ADDITIONAL
 STORY,THAT WOULD INCLUDE THE 3RD FLOOR.*
  
 5} MANY OF THE APPLIANCES THAT WERE
 LISTED IN THE ORIGINAL CALC'S HAVE BEEN
 DELETED FROM THE RESUB SET. PLEASE NOTE
 THAT IF THESE ARE ADDED BACK LATER A
 REVISED LOAD CALCULATION MUST BE
 RESUBMITTED AS A REVISION. PLEASE CHECK
 THE NUMBERS TO INSURE THE SERVICE WILL
 BE SUFFICIENT. THE ITEMS LEFT OFF TOTAL
 19480 WATTS. ALSO THE WATER HEATER
 APPEARS TO BE UNDERSIZED FOR THE SIZE
 OF THE RESIDENCE.
  
 6} THE RATINGS OF THE A/C EQUIPMENT ON
 THE ELECTRICAL CALC AND THE MECHANICAL
 SHEETS DO NOT CORRESPOND. IF THE
 MECHANICAL SHEETS ARE CORRECT THERE IS
 A 10 KW ERROR IN THE LOAD CALC'S.PLEASE
 CORRELATE THE INFORMATION. CHECK THE
 CALC'S!
  
 7} PLEASE REMOVE THE #2 GND CONUCTOR
 FROM THE METER TO THE MAIN DISCONNECTS
 PER 250.4(B). IT CREATES A PARALLEL
 GROUND PATH.
  
 8} RECEPTACLES NEED TO BE ADDED IN BED
 ROOMS #2 & 3 TO COMPLY WITH 210.52.
  
 9} THE DISCONNECTS AT THE CONDENSING
 UNITS DO NOT APPEAR TO COMPLY WITH
 110.26.
  
 10} THE DATE THE PLANS WERE SEALED MUST
 BE ON THE TITLE BLOCK.61G-16.004(4).*
  
 NOTE: THE COMMENTS FOLLOWED BY AN
 ASTERISK WERE ON THE PREVIOUS REVIEW.
 SEE FS. 553.80(2)(B), ATTACHED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026