Plan Review Notes
Plan Review Notes For Permit 04030532
Permit Number 04030532
Review Stop E
Sequence Number 1
Notes
Date Text
2004-03-26 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALL-ED. MAINS/BRKRS AND PANELS ARE
 ALL TO BERATED FOR THE AVAILABLE FAULT
 CURRENT.
 PER 110.9/215.5
  
 2} LOAD CALCS ARE INCOMPLETE, THERE ARE
 NO TOTALS, AIR CONDITIONING TABLES ARE
 EMPTY.
  
 3} PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 4} PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 5} PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52(E).
  
 6} PLEASE SHOW COMPLIANCE FOR
 DISCONNECTING MEANS PER 225.31, FOR
 "STORAGE" BLDG.
  
 7} THERE IS NO CIRCUIT LISTED ON PANEL
 SCHEDULE OR CALCULATION FOR THE
 ELEVATOR EQUIPMENT.
  
 8} PLEASE SEE MISSING RECEPT REQUIRED
 FOR A/C EQUIPMENT. 210.63
  
 9} PLEASE INDICATE COMPLIANCE WITH
 NFPA-72 & THE FLORIDA BUILDING CODE AND
 PLACE SMOKE DETECTORS IN ALL REQUIRED
 LOCATIONS.
  
 10} PLEASE NOTE THAT TWO OF THE
 RECEPTACLES AROUND THE POOL DO NOT
 COMPLY WITH THE 10' MINIMUM, ARTICLE
 680.22(A)(2).
  
 11} PLEASE SEE RECEPTACLES SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
  
 12} PLEASE NOTE PER 61G1-16.004(4), THE
 DATE SEALED MUST BE ON THE TITLE BLOCK.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved