| Date |
Text |
| 2004-03-26 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALL-ED. MAINS/BRKRS AND PANELS ARE |
| | ALL TO BERATED FOR THE AVAILABLE FAULT |
| | CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 2} LOAD CALCS ARE INCOMPLETE, THERE ARE |
| | NO TOTALS, AIR CONDITIONING TABLES ARE |
| | EMPTY. |
| | |
| | 3} PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 4} PLEASE LIST THE REQUIRED ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 5} PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52(E). |
| | |
| | 6} PLEASE SHOW COMPLIANCE FOR |
| | DISCONNECTING MEANS PER 225.31, FOR |
| | "STORAGE" BLDG. |
| | |
| | 7} THERE IS NO CIRCUIT LISTED ON PANEL |
| | SCHEDULE OR CALCULATION FOR THE |
| | ELEVATOR EQUIPMENT. |
| | |
| | 8} PLEASE SEE MISSING RECEPT REQUIRED |
| | FOR A/C EQUIPMENT. 210.63 |
| | |
| | 9} PLEASE INDICATE COMPLIANCE WITH |
| | NFPA-72 & THE FLORIDA BUILDING CODE AND |
| | PLACE SMOKE DETECTORS IN ALL REQUIRED |
| | LOCATIONS. |
| | |
| | 10} PLEASE NOTE THAT TWO OF THE |
| | RECEPTACLES AROUND THE POOL DO NOT |
| | COMPLY WITH THE 10' MINIMUM, ARTICLE |
| | 680.22(A)(2). |
| | |
| | 11} PLEASE SEE RECEPTACLES SERVING |
| | KITCHEN COUNTERSPACE TO MEET 210.52C- |
| | SEC'S 1,2,3,4 AND 5 |
| | |
| | 12} PLEASE NOTE PER 61G1-16.004(4), THE |
| | DATE SEALED MUST BE ON THE TITLE BLOCK. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |