| Date |
Text |
| 2004-04-19 00:00:00 | DENIED |
| | 1. THE NOTICE OF COMMENCEMENT SHALL BE |
| | RECORDED AT PALM BEACH COUNTY |
| | COURTHOUSEAND A COPY SUBMITTED TO THIS |
| | OFFICE |
| | BEFORE A PERMIT CAN BE ISSUED.BLANK |
| | FORMS ARE AVAILABLE FROM THIS OFFICE. |
| | |
| | 2. BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 3.ENERGY CALCS NOT SIGNED. |
| | |
| | 4.BUILDING VALUATION TOO LOW BASED |
| | UPON SBCCI BUILDING VALUATION TABLES. |
| | THE REVISED VALUATION IS $398,463. |
| | ADDITIONAL PERMIT FEES ARE DUE. |
| | |
| | 5.SPIRAL STAIRWAYS. FBC 1007.8.2.1 6. |
| | THE TURN OF THE STAIRWAY SHALL BE SUCH |
| | THAT DESCENDING USERS HAVE THE OUTER |
| | HANDRAIL AT THEIR RIGHT SIDE.REVISE |
| | PLAN TO SHOW THIS. |
| | |
| | 6.EXIT REQIREMENTS.FBC 1005 |
| | BEDROOM EGRESS WINDOWS SHALL COMPLY |
| | WITH THIS SECTION. WINDOWS LISTED DO |
| | NOTMEET EMERGENCY ESCAPE AND RESCUE |
| | OPENINGREQUIREMENTS. |
| | 23,25,34,35,36,37,38,9,10,14,15,19.I |
| | CHECKED THESES AGAINST PGT EGRESS SIZE |
| | SUMMARY CHARTS. |
| | |
| | 1015.2 HEIGHT. GUARDRAILS SHALL |
| | FORM A VERTICAL PROTECTIVE BARRIER NOT |
| | LESS THAN 42" HIGH. |
| | 1015.3 OPENINGS. OPEN GUARDRAILS |
| | SHALL HAVE INTERMEDIATE RAILS OR ORNA- |
| | MENTAL PATTERNS SUCH AS A 4" DIAMETER |
| | SPHERE CAN NOT PASS THROUGH. A BOTTOM |
| | RAIL OR CURB SHALL BE PROVIDED THAT |
| | WILLREJECT THE PASSAGE OF 2" DIAMETER |
| | SPHERE. |
| | SHOW DETAIL ON PLAN. |
| | |
| | 8.SPECIFY CONSTRUCTION TYPE IS IT |
| | TYPE 5 OR TYPE 6 1 HR. PROTECTED. |
| | |
| | 9.SPRINKLERS REQUIRED PER TABLE 600 |
| | FBC.SUBMIT SHOP DRAWINGS. |
| | |
| | 10.SHOW ELEVATOR SHAFT PROTECTION |
| | DETAIL. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | ART LANGE |
| | BUILDING PLANS EXAMINER |
| | 805-6672 |