| Plan Review Notes For Permit 04030493 |
| Permit Number |
04030493 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-04-07 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE PROVIDE PANEL SCHEDULE AND | | | CALCULATIONS FOR NEW PANELS "EM" AND | | | "GEN". | | | | | | 2} SHOW CIRCUIT NUMBERS AND PANEL OF | | | ORIGIN FOR LIGHTS AND DEVICES BEING | | | ADDED(RE: RECESSED AND TYPE "V" LIGHTS) | | | ON SHEET E-2. | | | | | | 3} PLEASE PROVIDE A CALCULATION INCLUDI | | | NG ALL ADDED LOADS IMPOSED,AND EXISTING | | | LOADS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|