2004-03-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHTS PB-1, P-1, & P-2 WATER FILTERS
 SHALL COMPLY WITH NSF-42 PER SECTION
 611.1. SUBMIT MANUF. SPECIFICATION SHEET
 SHOWING COMPLIANCE. WATER & GAS PIPING
 GENERAL NOTES "F" STATES "OR EQUAL".
 THIS IS NOT APPROVED.
 2) SHTS P-3 & P-4 SANITARY WASTE PIPING
 KEY NOTES #9 SAFE WASTE NOT APPROVED.
 NO DOUBLE TRAPING PER SECTION 1001.1.
 FLOOR SINK SHALL BE CONNECTED TO VENTED
 LINE IN COMBINATION WASTE & VENT SYSTEM
 SECTION 912.2.2 NOT TO ANOTHER FLOOR
 SINK LINE.
 3) SEPARATE GAS PERMIT REQUIRED.
 4) ALL CAPPED PLUMBING & GAS LINES SHALL
 BE INSPECTED PRIOR TO COVERING.
 5) PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025 - INITIALS ARE NOT ACCEPTABLE
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  