2004-04-09 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04030492
 ADD: 10130 NORTHLAKES BLVD# 651
 CONT: OAK CONSTRUCTION
 TEL: (954)610-2774
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE NEW RAMP ON THE N.W. CORNER OF
 THE BUILDING MUST MEET FL ACCESSIBILITY
 REQUIREMENTS:
 A)11-4.8.4.(2) LANDINGS. ALL
 LANDINGSON RAMPS SHALL NOT BE LESS THAN
 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARENCE.EQ1 DOESN'T GIVE THE
 REQUIREMENTS FOR THE BOTTOM LANDING,
 NOTDRAWN IN, A-9 SECTION 2 INDICATES TO
 MATCH ASPHALT SURFACE!
 B)11-4.8.4(3) IF RAMPS CHANGE DIREC-
 TION AT LANDINGS, THE MINIMUM LANDING
 SIZE SHALL BE 60" X 60". LANDING
 ALREADYEXIST BUT IF IT DOESN'T MEET
 THIS REQUIRMENT IT MUST BE REDESIGNED.
 C)11.4.8.5. HANDRAILS: IF A RAMP HAS
 A RISE GREATER THAN 6" OR A HORIZONTAL
 PROJECTION GREATER THAN 72", THEN IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 2) LOUNGE ENTRY DOOR 18" PULL SIDE:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 3) MENS RESTROOM# 116 ENTRY DOOR PULL
 SIDE 18", SEE 11-4.13.6.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026