| 2004-03-23 00:00:00 | |
| | UNSAT |
| | ~~~~~ |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE SEE THE TOTAL AMPS IN THE LOAD |
| | CALCULATION IS 380 AMPS (SHEET E-3), |
| | THE SERVICE CONDUCTOR SIZE ON SHEET E-2 |
| | IS 400 MCM WHICH PER TABLE 310.16 @ 335 |
| | AMPS, IS NOT RATED FOR THE LOAD SERVED. |
| | |
| | 2} THE"#4/OG" CONDUCTOR LISTED ON THE |
| | RISER SHEET E-2, BEING RAN WITH THE |
| | FEEDER IS INCORRECT PER 250.122 IF IT |
| | IS SUPPOSED TO BE THE EQUIPMENT GROUND. |
| | |
| | 3} THE TOTAL KW AS COMPUTED ACROSS FOR |
| | L2N,N2NA & N2N DOES NOT SEEM TO ADD |
| | CORRECTLY, PLEASE CHECK.SHEET E-3. |
| | |
| | 4} CONTINUOUS LOADS SUCH AS LIGHTING |
| | MUST BE CALCULATED PER 210.19(A), |
| | 210.20(A) AND 215.2(A). PLEASE ADDRESS |
| | THIS IN THE CALCULATIONS. |
| | |
| | 5} PLEASE INDICATE THE LIGHTING BRANCH |
| | CIRCUIT NUMBERS AND THE CIRCUITING FOR |
| | THE LIGHTS ON SHEET E-1. |
| | |
| | 6} PLEASE REFER TO NOTE #10 ON SHEET |
| | E-3. THE REVERENCE TO ARTICLE 380-8(B), |
| | IS A 1999 CODE REVERENCE. PLEASAE BE |
| | ADVISED THAT WEST PALM BEACH HAS |
| | ADOPTED THE 2002 NEC. SEE ARTICLE |
| | 404.8(B). |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |