| 2004-03-09 00:00:00 | 1) ALL NEW REQUIRED STAIRS AND RAMPS |
| | SHALL BE PROVIDED WITH HANDRAILS. |
| | |
| | 2) PANIC HARDWARE REQUIRED AT ALL |
| | DOORS SUBJECT TO AN OCCUPANCY OF 100 |
| | OR MORE PERSONS. |
| | |
| | 3) SINCE THE BUILDING IS NOT FIRE |
| | SPRINKLER PROTECTED, ALL ELECTRICAL, |
| | MECHANICAL, AND SERVICE ROOMS SHALL |
| | BE ONE HOUR RATED WITH 45 MINUTE |
| | OPENING PROTECTIVES. |
| | |
| | 4) SOME STAIRS ON PAGE A-2.0 ARE |
| | ABSENT OF HANDRAILS. |
| | |
| | 5) ALL DEMOLITION, RENOVATION, AND |
| | CONSTRUCTION TO COMPLY WITH NFPA 241. |
| | |
| | 6) EXITS SHALL REMAIN CLEAR. |
| | |
| | 7) DEBRIS SHALL BE REMOVED DAILY |
| | FROM INSIDE THE BUILDING. |
| | |
| | 8) BUILDING ADDRESS REQUIRED. A MINIMUM |
| | 6" NUMBERS ARE REQUIRED. |
| | |
| | 9) PLEASE PROVIDE PRESCRIPTIVE |
| | STRENGTH REQUIREMENTS FOR ALL |
| | HANDRAILS AND GUARDRAILS. |
| | |
| | 10) GASOLINE POWERED EQUIPMENT USED |
| | DURING DEMOLITION ACTIVITIES SHALL |
| | BE PROVIDED WITH ADEQUATE VENTILATION |
| | TO PREVENT THE ACCUMULATION OF |
| | CARBON MONOXIDE. |
| | |
| | 11) PLEASE FURTHER DEFINE EXISTING |
| | EMERGENCY LIGHTS AND EXIT SIGNS IN |
| | SACRISITY 002, AND ALTAR 001. |
| | |
| | 12) NO EMERGENCY LIGHTS IN PAVILLION |
| | 100. |
| | |
| | 13) PLEASE PROVIDE DETAILS ABOUT THE |
| | REQUIRED FIRE ALARM SYSTEM. THE |
| | PROPOSED OCCUPANT LOAD EXCEEDS 300 |
| | PERSONS, SO A FIRE ALARM SYSTEM IS |
| | REQUIRED. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |