Plan Review Notes
Plan Review Notes For Permit 04030467
Permit Number 04030467
Review Stop B
Sequence Number 1
Notes
Date Text
2004-04-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04030467
 ADD: 4500 S DIXIE HWY
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITEY KNOWN, OR IS IN
 QUESTIONTHE BUILDING OFFICIAL MAY
 REQUIRE EXPLORATIONS, TEST OR OTHER
 ADEQUATE PROOF AS TO THE PERMISSIBLE
 SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) TABLE 600 ISSUES, INTERPRETATION BY
 NEIL MELLICK B.O. FOR THE PURPOSES OF
 THIS REVIEW THE SANCTUARY AND PAVILLION
 ARE SEPERATE BUILDINGS CONNECTED BY A
 COVERED WALKWAY. SEE FBC CHAPTER 2 FOR
 DEFINITION OF "WALKWAY, COVERED".
 A ASSUMED PROPERTY LINE WILL NEED TO
 BE DECIDED BETWEEN THE 2 BUILDINGS &
 A MINIMUM BUILDING TYPE, WITH THIS
 INFORMATION THE MINIMUM HOUR RATING ON
 THE
 EXTERIOR WALLS AND ALLOWABLE OPENING
 SIZES CAN BE DETERMINED.
  
 4) INTERPRETATION BY NEIL MELICK B.O.,
 THE PLANS INDICATE THAT THE SANCTUARY
 WILL NOT NEED THE FIRE SPRINKLERS AS
 STATED ON SHEET ON A-2.0, 903.7.2.4.
 EXCEPTION# 1 SANCTUARY, A PLACE OF
 WORSHIP.
 THE PAVILION WILL BE CONSIDERED AS A
 SEPERATE BUILDING, TABLE 1003.1
 DETERMINES MINIMUM OCCUPANT LOAD.
 ASSEMBLY OCCUPANCY, WITHOUT FIXED SEAT-
 ING, IS 7SQFT.THIS LOADING WILL
 FIGURE TO BE (70'X37') 370 PEOPLE. SINCE
 THIS STRUCTURE MAY BE USED FOR OTHER
 USES THAN WORSHIP IT DOES NOT MEET THE
 EXCEPTION FOR FIRE SPRINKLERS. PROVIDE
 A FIRE SPRINKLER PLAN THAT MEETS NFPA 13
 SEE 903.7.2.4, ASSEMBLY WITH A OCCUPANT
 LOAD OF GREATER THAN 300.
  
 5) THIS COMMENT WILL APPLY TO BOTH
 COVERED DRIVE AND DROP OFF. THE PASSEN-
 GER LOADING ZONE (11-4.6.6) NEEDS TO
 HAVE EITHER:
 A) A 5'-0"X20'-0" PASSENGER LOADING
 ZONE NEXT TO THE 12'-0" VEHICLE PULL-UP
 SPACE.
 B) SHEET A-3.1 & A-3.3 INDICATE A CURB
 CUT COMPLYING WITH 11-4.7 BUT IS MISSING
 THE ACCESS ISLE. 11-4.6.6 DOES ALLOW A
 CURB BETWEEN THE ACCESS AISLE AND THE
 VEHICLE PULL-UP ZONE PROVIDED THE WIDTH
 OF THE RAMP IS 20'-0" WIDE PLUS THE
 FLARED SIDES.
  
 6) SCHOOL DROP OFF ZONE AND COVERED
 PARKING. THREE ACCESSIBILITY ISSUES:
 A) SHEET A-3.3, PARKING STRUCTURES,
 11-4.1.2(5)(B) THERE SHALL BE AT LEAST
 (1) VAN ACCESSIBLE PARKING SPACE.
 B) SHEET A-5.1 THE VAN ACCESSIBLE PARK-
 ING SPACE, VERTICAL CLEARENCE OF 98",
 SEE 11-4.6.5
 C) THE SAME DETAIL, THE DROP OFF ZONE,
 (11-4.6.5) THE MINIMUM VERTICAL DIMEN-
 SION SHALL BE 114".
  
 7) NOTE CURB RAMPS, 11-4.7.7 DETECTABLE
 WARNINGS, A CURB RAMP SHALL HAVE A
 DETECTABLE WARNING COMPLYING WITH
 11-4.29.2. THE DETECTABLE WARNING SHALL
 EXTEND THE FULL WIDTH & DEPTH OF THE
 CURB RAMP.
  
 8) STAIRWAY CONSTRUCTION SEE A-10.0
 DETAIL# 5, THE DETAIL INDICATES THE USE
 OF WOOD STRINGERS,1007.1.1(3) THE USE OF
 WOOD STRINGERS IS PROHIBITED WHEN MORE
 THAN 40 PEOPLE ARE ABOVE THE LEVEL OF
 EXIT DISCHARGE.
  
 9) STAIRWAY CONSTRUCTION/ MEZZANINE
 1005.7.3 (1) EXCEPTION REQUIRES A SMOKE
 DETECTION SYSTEM IN ACCORDANCE WITH
 NFPA 72.
  
 10) PLANS ARE TO INDICATE WIND DESIGN:
 FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 11)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) DOORSWING & ROLL UP
 C) ROOF ASSEMBLIES
 D) TRUSS ANCHORS
  
 12) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 13)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved