| Date |
Text |
| 2004-07-10 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) FROM PREVIOUS REVIEW, SHT A-1 PER |
| | TABLE 403.1 A DRINKING FOUNTAIN IS REQ- |
| | UIRED IN EACH SPACE. ALSO SEE SECTION |
| | 410.1. - RESPONSE NOTED, BUT THE DRINK- |
| | ING FOUNTAIN OR A BOTTLED WATER COOLER |
| | IS REQUIRED. PLANS SHOW A DRINKING FOUN- |
| | TAIN ROUGHED IN ON SANT. AND WATER |
| | RISER DIAGRAMS, BUT (OPT.) WRITTEN IN |
| | AFTER. PLEASE CLARIFY. EITHER ONE OR THE |
| | OTHER SHALL BE CALLED OUT ON PLANS. |
| | SECTION 104.2.1. |
| | 2) FROM PREVIOUS REVIEW, SHT A-1 BREAK |
| | ROOM SINK SHALL COMPLY WITH SECTION 11- |
| | 4.24 AND ALL SUBSECTIONS. SUBMIT A DE- |
| | TAIL. RESPONSE NOTED, BUT THE FOLLOWING |
| | SUBSECTIONS WERE NOT ADDRESSED. SECTION |
| | 11-4.24.3 KNEE CLEARANCE, 11-4.24.4 |
| | DEPTH, 11-4.24.5 CLEAR FLOOR SPACE, |
| | 11-4.24.6 EXPOSED PIPES AND SURFACES. |
| | PLEASE ADDRESS THESE SECTIONS. SECTION |
| | 104.2.1 |
| | 3) FROM PREVIOUS REVIEW, SUBMIT CALCUL- |
| | ATIONS FOR ROOF DRAINS PER SECTION 1106 |
| | AND ALL SUBSECTIONS. SHOW SQUARE FEET |
| | FOR ROOF AREA, AND 1/2 AREA OF ALL VERT- |
| | ICAL WALLS INCLUDING PARAPETS AND ROOF |
| | AREAS THAT DRAIN ONTO THE ROOF AREA FROM |
| | ABOVE ADDED TO CALCULATIONS. GUTTERS |
| | SHALL BE SIZED PER TABLE 1106.6. SHOW |
| | SLOPE OF GUTTERS AND INDICATE LOCATION |
| | OF HIGH POINTS AND LOW POINT OF GUTTERS. |
| | NO RESPONSE WAS NOTED FOR THIS COMMENT. |
| | 4)A PROFESSIONAL ENGINEER SHALL SIGN HIS |
| | NAME AND AFFIX HIS SEAL TO ALL PLANS, |
| | SPECIFICATIONS, REPORTS AND FINAL BID |
| | DOCUMENTS PROVIDED TO THE OWNER OR THE |
| | OWNER'S REPRESENTATIVE, OR OTHER DOCU- |
| | MENTS PREPARED OR ISSUED BY SAID REGIS- |
| | TRANT AND BEING FILED FOR PUBLIC RECORD. |
| | THE DATE THAT THE SIGNATURE AND SEAL IS |
| | AFFIXED AS PROVIDED HEREIN SHALL BE EN- |
| | TERED ON SAID PLANS, SPECIFICATIONS, RE- |
| | PORTS, OR OTHER DOCUMENTS IMMEDIATELY |
| | UNDER THE SIGNATURE OF THE PROFESSIONAL |
| | ENGINEER, FAC 61G15-23.002(1) |
| | FS 471.025 - PER DBPR INITIALS ARE NOT |
| | APPROVED. |
| | EACH SHEET OF PLANS AND PRINTS WHICH |
| | MUST BE SEALED UNDER THE PROVISIONS OF |
| | CHAPTER 471 SHALL BE SEALED, SIGNED AND |
| | DATED BY THE PROFESSIONAL ENGINEER IN |
| | RESPONSIBLE CHARGE. FAC 61G15-23.002(2) |
| | FS 471.025 - FULL SIGNATURE IS REQUIRED |
| | IF THIS IS YOUR LEGAL SIGNATURE, SUBMIT |
| | PROOF BY SENDING COPY OF DRIVERS LICENSE |
| | OR OTHER LEGAL PROOF, PLUS A NOTORIZED, |
| | SIGNED SEALED LETTER FOR OUR FILES. |
| | *********WHEN RESUBMITTING PLANS******** |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |