Plan Review Notes
Plan Review Notes For Permit 04030451
Permit Number 04030451
Review Stop P
Sequence Number 2
Notes
Date Text
2004-07-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) FROM PREVIOUS REVIEW, SHT A-1 PER
 TABLE 403.1 A DRINKING FOUNTAIN IS REQ-
 UIRED IN EACH SPACE. ALSO SEE SECTION
 410.1. - RESPONSE NOTED, BUT THE DRINK-
 ING FOUNTAIN OR A BOTTLED WATER COOLER
 IS REQUIRED. PLANS SHOW A DRINKING FOUN-
 TAIN ROUGHED IN ON SANT. AND WATER
 RISER DIAGRAMS, BUT (OPT.) WRITTEN IN
 AFTER. PLEASE CLARIFY. EITHER ONE OR THE
 OTHER SHALL BE CALLED OUT ON PLANS.
 SECTION 104.2.1.
 2) FROM PREVIOUS REVIEW, SHT A-1 BREAK
 ROOM SINK SHALL COMPLY WITH SECTION 11-
 4.24 AND ALL SUBSECTIONS. SUBMIT A DE-
 TAIL. RESPONSE NOTED, BUT THE FOLLOWING
 SUBSECTIONS WERE NOT ADDRESSED. SECTION
 11-4.24.3 KNEE CLEARANCE, 11-4.24.4
 DEPTH, 11-4.24.5 CLEAR FLOOR SPACE,
 11-4.24.6 EXPOSED PIPES AND SURFACES.
 PLEASE ADDRESS THESE SECTIONS. SECTION
 104.2.1
 3) FROM PREVIOUS REVIEW, SUBMIT CALCUL-
 ATIONS FOR ROOF DRAINS PER SECTION 1106
 AND ALL SUBSECTIONS. SHOW SQUARE FEET
 FOR ROOF AREA, AND 1/2 AREA OF ALL VERT-
 ICAL WALLS INCLUDING PARAPETS AND ROOF
 AREAS THAT DRAIN ONTO THE ROOF AREA FROM
 ABOVE ADDED TO CALCULATIONS. GUTTERS
 SHALL BE SIZED PER TABLE 1106.6. SHOW
 SLOPE OF GUTTERS AND INDICATE LOCATION
 OF HIGH POINTS AND LOW POINT OF GUTTERS.
 NO RESPONSE WAS NOTED FOR THIS COMMENT.
 4)A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025 - PER DBPR INITIALS ARE NOT
 APPROVED.
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025 - FULL SIGNATURE IS REQUIRED
 IF THIS IS YOUR LEGAL SIGNATURE, SUBMIT
 PROOF BY SENDING COPY OF DRIVERS LICENSE
 OR OTHER LEGAL PROOF, PLUS A NOTORIZED,
 SIGNED SEALED LETTER FOR OUR FILES.
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]