Date Text
2004-06-22 00:00:00******** UNSAT *******
  
 1)NOTE: PLEASE SEE CIRCUITING MISSING
 FOR EM/EXT LTS IN ONE UNIT.
 SEE HIGHLIGHTED SET.
  
 2)NOTE: PLEASE SEE FBC 104.2.1, PLANS
 ARE REQUIRED TO HAVE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 PLANS.
  
 3)NOTE: PLEASE CORRELATE A/C SYSTEMS
 WITH MECHANICAL PLANS.
 PLEASE SEE MECH SHEETS SHOW EACH UNIT
 W/ 10KW HEAT AND ELEC SHOWS 5KW.
 PLEASE ADJUST OCP/ AWG AND LOAD CALCS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  