2004-04-02 00:00:00DENIED:
 1.PROVIDE OUTSIDE AIR CALCULATIONS PER
 2001 FBC(M) 403.3.
  
 2.INDICATE OUTSIDE AIR INTAKE, DUCT
 SIZE, MATERIAL AND LAYOUT.PLEASE NOTE,
 FRESH AIR INTAKES SHALL BE LOCATED A
 MINIMUM OF 10 FT FROM LOADING DOCKS,
 PARKING LOTS, STREETS & ALLEYS.
  
 3.PROVIDE MOUNTING DETAIL FOR THE
 CONDENSING UNITS LOCATED OF THE ROOF.
 PLEASE NOTE HEIGHT REQUIREMENT FOR
 STANDS SHALL COMPLY WITH 2001 FBC 1511.7
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.