| Notes |
| Date |
Text |
| 2004-03-26 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING | | | INSTALLED. MAINS/BRKRS AND PANELS ARE | | | ALL TO BE RATED FOR THE AVAILABLE FAULT | | | CURRENT, PER 110.9 & 10. | | | | | | 2} PROVIDE PANEL SCHEDULES FOR ALL | | | PANELS. | | | | | | 3} INDICATE NUMBER OF PHASES & VOLTAGE | | | OF SERVICE. | | | | | | 4} PLEASE USE THE LIGHTING LOAD PER 220. | | | 3(A). 3.5/SQ.FT, FOR OFFICE BLDG. | | | | | | 5} CALCULATE ALL CONTINUOUS LOADS PER | | | 215.2(A). | | | | | | 6} NOTE THAT THERE ARE NO DEMAND FACTORS | | | FOR COMMERCIAL HEATING EQUIPMENT. | | | | | | 7} RECEPTACLES ARE TO BE CALCULATED PER | | | 220.3(B)(11), 180VA. | | | | | | 8} INCLUDE CIRCUIT NUMBER AT EQUIPMENT & | | | DEVICES ON DRAWINGS. | | | | | | 9} INDICATE COMPLIANCE WITH 700.12(E) ON | | | EM. LIGHT CIRCUIT NUMBERS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|