Plan Review Notes
Plan Review Notes For Permit 04030451
Permit Number 04030451
Review Stop E
Sequence Number 1
Notes
Date Text
2004-03-26 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT, PER 110.9 & 10.
  
 2} PROVIDE PANEL SCHEDULES FOR ALL
 PANELS.
  
 3} INDICATE NUMBER OF PHASES & VOLTAGE
 OF SERVICE.
  
 4} PLEASE USE THE LIGHTING LOAD PER 220.
 3(A). 3.5/SQ.FT, FOR OFFICE BLDG.
  
 5} CALCULATE ALL CONTINUOUS LOADS PER
 215.2(A).
  
 6} NOTE THAT THERE ARE NO DEMAND FACTORS
 FOR COMMERCIAL HEATING EQUIPMENT.
  
 7} RECEPTACLES ARE TO BE CALCULATED PER
 220.3(B)(11), 180VA.
  
 8} INCLUDE CIRCUIT NUMBER AT EQUIPMENT &
 DEVICES ON DRAWINGS.
  
 9} INDICATE COMPLIANCE WITH 700.12(E) ON
 EM. LIGHT CIRCUIT NUMBERS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026